Outback Power Systems FX2012ET, VFX3024E, VFX3048E, VFX2612E Stacking Menu, PG2 AUX, Adv/Fx/Stack

Page 53

MATE SCREENS

STACKING MENU

The STACK (stacking) section is used to program the stacking of the FX’s as well as which ‘Slave’ FX’s will stay ON at all times (won’t go into ‘Power Save’ mode) and in what order the slave FX’s will come ON (if they are in ‘Power Save’ mode). An explanation of stacking can be found on pages 24-26 of this manual.

ADV/FX/PAGE1--------

choose category:

ADV

INV

CHGR

PG2

 

 

 

ADV/FX/PAGE2--------

choose category:

 

PG1

GRID

GEN

PG3

 

 

 

 

 

 

 

ADV/FX/PAGE3--------

choose category:

 

PG2

AUX

STACK

PG4

 

 

 

 

 

 

 

ADV/FX/STACK-----

P00

Stack 1-2ph Master phase

DOWN INC DEC PORT

ADV/FX/STACK-----

P00

power save level

0

master adjust only

DOWN

INC

DEC

PORT

 

 

 

ADV/FX/STACK-----

P00

power save level

1

slave adjust only

DOWN

INC

DEC

PORT

 

 

 

ADV/FX/STACK--------

stacking setup

 

 

completed

 

 

TOP

ADV

MAIN

Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is displayed. Selecting <PG2> shows a second screen of categories.

Selecting <PG3> shows a third screen of categories.

Selecting <STACK> allows adjustment of the stacking set points and operation.

The STACK PHASE screen sets the hierarchy of the FX’s. If the system is to be stacked, a HUB must be included and the FX that is to be the MASTER must be plugged into port 1 of the HUB. The default for every FX is ‘1-2ph Master’. Pressing PORT will select the next port that an FX is plugged into. When the port for the slave FX has been chosen, press INC to cycle through the slave options (Classic Slave, OB Slave L1, OB Slave L2, 3ph Master, and 3ph Slave).

The POWER SAVE LEVEL MASTER ADJUST is used to set the number of FX SLAVE’s that will remain on under any load condition. The value corresponds to the rank of the SLAVE. For example, setting this value to 2 allows all slaves with POWER SAVE LEVEL SLAVE ADJUST ONLY values 2 or less to stay on at all times. Setting this number to a low value will result in fewer FX’s remaining on and will provide the highest system efficiency.

The POWER SAVE LEVEL SLAVE ADJUST is used to set a slave FX’s priority for operation when the complete system is operating at medium to heavy loads. By setting each of the slaves to a different number you can control the sequence that the slave FX’s are turned on by the master FX.

Selecting TOP returns the user to the top of the ADV/FX/STACK menu section. Selecting ADV returns you to the advanced screen to allow selection of another product connected to the MATE. Selecting MAIN returns the display to the MAIN screen.

Copyright 2003  OutBack Power Systems, Inc.

FX & VFX “E” Series Inverter/Charger System

Installation & Programming Manual

19009 62nd Ave NE, Arlington WA 98223 USA

900-0027-2

 

Tel 360 435 6030 Fax 360 435 6019

Rev 7.1 06/08/06

Page 53

Image 53
Contents Export FX and VFX Inverter/Charger Installation and Programming Manual900-0027-2 Table of Contents Mate Screens Wire Sizes Warranty RegistrationStacking Instructions Declaration of Conformity EU Declaration of ConformityImportant Safety Instructions Installation GuidelinesAdditional Notices General PrecautionsPersonal Precautions While Working with Batteries Ratings AC Input Frequency Range Maximum Continuous Output PowerMaximum AC Output Current Maximum Overcurrent Protection AmpacityACA DCC DCA MountingComplete Outback Integrated Systems Psac Psdc PS2AC PS2DCAC Wiring Connections Battery Temp Remote Temperature Sensor RTS Indicators / Control WiringInverter ON/OFF Auxiliary Output AUX + / AUXDC Battery Terminals Battery FX CablingBattery Terminal Covers Equipment Ground TerminalsFXA Accessory KIT FX AccessoriesFX-ACA AC Conduit Adapter FX-DCA DC Conduit AdapterSlave Master HUB Communication ManagerTurbo KIT Information Single FX System FX System Configuration Single FX SystemParalleled Dual FX System FX System Configuration Paralleled Dual FX SystemParalleled Quad FX System FX System Configuration Paralleled Quad FX SystemFX System Configuration 3 Phase FX System Phase FX SystemSTART-UP & Operation Battery Charging Set Points Battery Charging InstructionsStacking Procedure OutBack & 3-phase Stacking MethodsStack Phase Stacking InstructionsPower Save Level Slave Adjust only Power Save Level Master Adjust onlySystem Examples Stacked System Using OUTBACK’S Parallel StackingPhase Stacked System 3 FX’S only Automatic Generator Start Instructions OutBack Mate System Controllers Mate System Controller and DisplayOutBack Mate Menu Structure SETUP/FX/INPUT---P00Mate Buttons GEN‘SOFT’ Keys TOP Setup MainGEN Down Grid GENOFF Srch on OK Inverter ControlInverter Control AC Input Control Mate Menu MAP Mate Menu MAP Summary Screen SUM Status Setup ADVMate Screens ExamplesModes Menu Status ScreensFX MX ModesDown Meter MenuDown UP MeterBatt Battery MenuError Error MenuWarn WarnDiscon Disconnect MenuSell Sell MenuPG3 Search Menu Setup ScreensSrch Input SrchInput Menu INC DEC Port SETUP/FX/INPUTSrch Input Main InputAdvanced Screens Password Code 1 4PG2 PG4Downmore Inverter MenuINV Down INC Charger MenuPG1 Grid MenuGrid GEN PG3 ADV/FX/GRIDOFF Port Generator MenuPG1 Grid ADV INV Chgr PG2 Auxiliary MenuPG2 AUX Stack PG4 Down INC PortDEC Port PG2 AUX Stacking MenuStack ADV/FX/STACKSell CAL END of Advanced Menu SystemCalibration Menu AWG Wire SizesWarranty Two Year Limited Warranty900-0027-2 Registration Extended Warranty Application