MATE SCREENS

CALIBRATION MENU

The CAL (calibration) section is used in the factory or field to make fine adjustments in the operation of the FX. It is particularly useful when multiple FX’s are connected together in the different stacking configurations to maximize the performance of the FX’s.

In most cases, the user will not need to adjust these settings from the factory default values.

ADV/FX/PAGE1--------

choose category:

ADV INV CHGR PG2

ADV/FX/PAGE2--------

choose category:

PG1 GRID GEN PG3

ADV/FX/PAGE3--------

choose category:

 

PG2

AUX

STACK

PG4

 

 

 

 

 

ADV/FX/PAGE4--------

 

choose category:

 

 

PG3

SELL

CAL

MAIN

 

 

 

 

 

 

 

 

 

 

 

 

ADV/FX/CALIBRATE-P00

 

vac input

230 vac

 

adjustment

 

 

 

DOWN

INC

DEC

PORT

 

 

 

 

 

 

 

 

 

ADV/FX/CALIBRATE-P00

vac output

230 vac

adjustment

 

DOWN INC

DEC PORT

ADV/FX/CALIBRATE-P00 battery vdc 12.8 vdc adjustment

DOWN INC DEC PORT

ADV/FX/CALIBRATION-- calibration setup completed

TOP ADV MAIN

Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is displayed. Selecting <PG2> shows a second screen of categories.

Selecting <PG3> shows a third screen of categories.

Selecting <PG4> shows a fourth screen of categories.

Selecting <CAL> allows calibration of the AC input, AC output, and battery voltage set points.

The VAC INPUT ADJUSTMENT allows calibration of the AC input voltage. If the AC source is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised by pressing the INC button. Conversely, this value can be lowered by pressing the DEC button. The value can be raised or lowered 4 vac.

The VAC OUTPUT ADJUSTMENT allows calibration of the AC output voltage. If the AC output is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised up to 4 vac by pressing the INC button and lowered up to 4 vac by pressing the DEC button. NOTE: Only affects MATE's voltage display - See page 47 [ADJ. OUTPUT VOLTAGE] for actual adjustment of inverter VAC output.

The BATTERY VDC ADJUSTMENT allows calibration of the battery voltage. If the battery voltage is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised by pressing the INC button. Conversely, this value can be lowered by pressing the DEC button. The value can be raised or lowered 0.2 vdc.

Selecting TOP returns the user to the top of the ADV/FX/CALIBRATION menu section. Selecting ADV returns you to the advanced screen to allow selection of another product connected to the MATE. Selecting MAIN returns the display to the MAIN screen.

END OF ADVANCED MENU SYSTEM

Copyright 2003  OutBack Power Systems, Inc.

FX & VFX “E” Series Inverter/ Charger System

Installation & Programming Manual

19009 62nd Ave NE, Arlington WA 98223 USA

900-0027-2

 

Tel 360 435 6030 Fax 360 435 6019

Rev 7.1 06/08/06

Page 55

Image 55
Contents Export FX and VFX Inverter/Charger Installation and Programming Manual900-0027-2 Table of Contents Stacking Instructions Wire Sizes Warranty RegistrationMate Screens Declaration of Conformity EU Declaration of ConformityImportant Safety Instructions Installation GuidelinesPersonal Precautions While Working with Batteries General PrecautionsAdditional Notices Ratings Maximum Overcurrent Protection Ampacity Maximum Continuous Output PowerAC Input Frequency Range Maximum AC Output CurrentACA DCC DCA MountingComplete Outback Integrated Systems Psac Psdc PS2AC PS2DCAC Wiring Connections Auxiliary Output AUX + / AUX Indicators / Control WiringBattery Temp Remote Temperature Sensor RTS Inverter ON/OFFEquipment Ground Terminals Battery FX CablingDC Battery Terminals Battery Terminal CoversFX-DCA DC Conduit Adapter FX AccessoriesFXA Accessory KIT FX-ACA AC Conduit AdapterSlave Master HUB Communication ManagerTurbo KIT Information Single FX System FX System Configuration Single FX SystemParalleled Dual FX System FX System Configuration Paralleled Dual FX SystemParalleled Quad FX System FX System Configuration Paralleled Quad FX SystemFX System Configuration 3 Phase FX System Phase FX SystemSTART-UP & Operation Battery Charging Set Points Battery Charging InstructionsStacking Instructions OutBack & 3-phase Stacking MethodsStacking Procedure Stack PhasePower Save Level Slave Adjust only Power Save Level Master Adjust onlyPhase Stacked System 3 FX’S only Stacked System Using OUTBACK’S Parallel StackingSystem Examples Automatic Generator Start Instructions OutBack Mate System Controllers Mate System Controller and DisplayOutBack Mate GEN SETUP/FX/INPUT---P00Menu Structure Mate ButtonsDown Grid GEN TOP Setup Main‘SOFT’ Keys GENInverter Control Inverter ControlOFF Srch on OK AC Input Control Mate Menu MAP Mate Menu MAP Examples SUM Status Setup ADVSummary Screen Mate ScreensModes Status ScreensModes Menu FX MXMeter Meter MenuDown Down UPBatt Battery MenuError Error MenuWarn WarnDiscon Disconnect MenuPG3 Sell MenuSell Srch Setup ScreensSearch Menu Srch InputInput INC DEC Port SETUP/FX/INPUTInput Menu Srch Input MainPG4 Password Code 1 4Advanced Screens PG2INV Inverter MenuDownmore Down INC Charger MenuGEN PG3 ADV/FX/GRID Grid MenuPG1 GridPG1 Grid Generator MenuOFF Port Down INC Port Auxiliary MenuADV INV Chgr PG2 PG2 AUX Stack PG4DEC Port ADV/FX/STACK Stacking MenuPG2 AUX StackSell Calibration Menu END of Advanced Menu SystemCAL AWG Wire SizesWarranty Two Year Limited Warranty900-0027-2 Registration Extended Warranty Application