Outback Power Systems VFX3024E, VFX3048E, VFX2612E, FX2024ET, FX2348ET, FX2012ET manual Disconnect Menu

Page 42

MATE SCREENS

DISCONNECT MENU

The FX includes a section that displays the reason for last DISCONNECT from the AC source. This is helpful if the FX rejects the AC source and the user wants an explanation and help on rectifying the problem. The FX will disconnect from an AC source if the AC source falls out of the FX’s frequency or voltage ranges. If the AC source disconnects from the FX and none of the reasons for disconnect are followed by a “Yes” it is possible that the AC source shut itself down (this is sometimes the case with smaller generators, or generators with an internal temperature “shutdown” switch).

MAIN----------------

6:54:42P

SUM STATUS SETUP ADV

STATUS--------------

choose product:

FX MX

STATUS/FX/PAGE1-----

choose category:

MODES METER BATT PG2

STATUS/FX/PAGE2-----

choose category:

PG1 ERROR WARN PG3

STATUS/FX/PAGE3-----

choose category:

PG2 DISCON SELL MAIN

STATUS/FX/DISCON-P00

acin freq No too high

DOWN STATUS PORT

STATUS/FX/DISCON-P00

acin freq

No

too low

 

DOWN UP TOP

PORT

STATUS/FX/DISCON-P00

acin

voltage

No

> max

 

DOWN

UP TOP

PORT

STATUS/FX/DISCON-P00

acin

voltage

No

< min

 

DOWN

UP TOP

PORT

STATUS/FX/DISCON----

end of DISCON menu

UP TOP STATUS

The MAIN screen is where the menu system starts. The four words in the bottom line of the display correspond to the four buttons located below the display. The word in BOLD on the bottom line indicates the selection used to advance the display to the next screen. Pressing the left two buttons simultaneously from anywhere in the menu will return you to this screen.

Allows selection of the product type:

<FX>

FX inverter/charger system

MX

MX60 PV MPPT charge controller

MODES

Status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ

METER

Provides the AC voltages and currents of the FX

BATT

Provides the battery voltage and charger set points and timers

<PG2>

Displays additional sections – ERRORS, WARNINGS and PG3

PG1

Returns to page 1 of the STATUS section

ERROR

Displays the different causes for errors and qualifies each cause with a Yes or No

WARN

Displays the different causes for warnings and qualifies each with a Yes or No

<PG3>

Displays additional sections – reason for last DISCONNECT and SELL

PG2

Displays additional sections – ERRORS, WARNINGS and PG3

<DISCON>

Displays the reason that the FX last disconnected from the AC source

SELL

Displays the code related to the reason for the last disconnection while selling

MAIN

Returns the user to the MAIN menu

The ACIN FREQ TOO HIGH screen displays a “Yes” if the FX gets disconnected from the AC source due to the frequency of the AC source exceeding 59 Hz. The MATE does not display the frequency of the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC source is a generator, it may be possible to adjust the frequency of the generator.

The ACIN FREQ TOO LOW screen displays a “Yes” if the FX disconnected from the AC source due to the frequency of the AC source being below 41 Hz. The MATE does not display the frequency of the AC source, but this can be verified using an oscilloscope. If this message occurs and the AC source is a generator, it may be possible to adjust the frequency of the generator.

The ACIN VOLTAGE > MAX screen indicates that the AC source’s voltage exceeded the maximum AC voltage the FX allows (270 vac default). This value can be adjusted in the ADVANCED menu, in the GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads from high voltage. If you expect significant voltage drop due to long cable runs, it may be safe to raise the limit.

The ACIN VOLTAGE < MIN screen indicates that the AC source’s voltage is below the minimum AC voltage the FX allows (208 vac default). This value can be adjusted in the ADVANCED menu, in the GRID or GEN sections (depending on your input type). The FX disconnects to protect the loads from low voltage. If your AC source operates near this voltage limit, it could affect the charging function (the FX backs off the charger if the AC voltage reaches the lower limit) and adjusting the limit lower may be in order.

Selecting TOP returns the user to the top of the STATUS/FX/DISCON menu section. Selecting STATUS returns to the STATUS screen to allow selection of another product.

Installation & Programming Manual

FX & VFX “E” Series Inverter/Charger System

Copyright 2003  OutBack Power Systems, Inc.

 

900-0027-2

19009 62nd Ave NE, Arlington WA 98223 USA

Page 42

Rev 7.1

06/08/06

Tel 360 435 6030 Fax 360 435 6019

Image 42
Contents Installation and Programming Manual Export FX and VFX Inverter/Charger900-0027-2 Table of Contents Wire Sizes Warranty Registration Stacking InstructionsMate Screens EU Declaration of Conformity Declaration of ConformityInstallation Guidelines Important Safety InstructionsGeneral Precautions Personal Precautions While Working with BatteriesAdditional Notices Ratings Maximum AC Output Current Maximum Continuous Output PowerAC Input Frequency Range Maximum Overcurrent Protection AmpacityMounting ACA DCC DCAPsac Psdc PS2AC PS2DC Complete Outback Integrated SystemsAC Wiring Connections Inverter ON/OFF Indicators / Control WiringBattery Temp Remote Temperature Sensor RTS Auxiliary Output AUX + / AUXBattery Terminal Covers Battery FX CablingDC Battery Terminals Equipment Ground TerminalsFX-ACA AC Conduit Adapter FX AccessoriesFXA Accessory KIT FX-DCA DC Conduit AdapterHUB Communication Manager Slave MasterTurbo KIT Information FX System Configuration Single FX System Single FX SystemFX System Configuration Paralleled Dual FX System Paralleled Dual FX SystemFX System Configuration Paralleled Quad FX System Paralleled Quad FX SystemPhase FX System FX System Configuration 3 Phase FX SystemSTART-UP & Operation Battery Charging Instructions Battery Charging Set PointsStack Phase OutBack & 3-phase Stacking MethodsStacking Procedure Stacking InstructionsPower Save Level Master Adjust only Power Save Level Slave Adjust onlyStacked System Using OUTBACK’S Parallel Stacking Phase Stacked System 3 FX’S onlySystem Examples Automatic Generator Start Instructions Mate System Controller and Display OutBack Mate System ControllersOutBack Mate Mate Buttons SETUP/FX/INPUT---P00Menu Structure GENGEN TOP Setup Main‘SOFT’ Keys Down Grid GENInverter Control Inverter ControlOFF Srch on OK AC Input Control Mate Menu MAP Mate Menu MAP Mate Screens SUM Status Setup ADVSummary Screen ExamplesFX MX Status ScreensModes Menu ModesDown UP Meter MenuDown MeterBattery Menu BattError Menu ErrorWarn WarnDisconnect Menu DisconSell Menu PG3Sell Srch Input Setup ScreensSearch Menu SrchSrch Input Main INC DEC Port SETUP/FX/INPUTInput Menu InputPG2 Password Code 1 4Advanced Screens PG4Inverter Menu INVDownmore Charger Menu Down INCGrid Grid MenuPG1 GEN PG3 ADV/FX/GRIDGenerator Menu PG1 GridOFF Port PG2 AUX Stack PG4 Auxiliary MenuADV INV Chgr PG2 Down INC PortDEC Port Stack Stacking MenuPG2 AUX ADV/FX/STACKSell END of Advanced Menu System Calibration MenuCAL Wire Sizes AWGTwo Year Limited Warranty Warranty900-0027-2 Extended Warranty Application Registration