Section 3 • Installation
Pressure Testing | NOTICE |
CAUTION
Do not hydro test compressur unit. Failure to comply
may result in damage to equipment.
CAUTION
The compressor unit along with other system units contain many components with various pressure ratings. Pressure relief protection provided considers the design pressure of a system components. Before replacing a pressure relief valve with a relief valve having a higher presure setting, all system
components must be evaluated for acceptability.
Pressure test in compliance with Chapter VI of the ASME B31.3 Process Piping Code.
Initial Oil Charging
Using Non
CAUTION
Do not mix oils. Failure to comply may result in
damage to equipment.
NOTICE
Vilter does not approve
Due to the need for adequate lubrication, Vilter recom- mends only the use of Vilter lubricants, designed spe- cifically for Vilter compressors. With extensive research that has been performed, we are able to offer gas com- pression lubricating oils. Use of oil not specified or sup- plied by Vilter will void the compressor warranty.
Please contact your local Vilter representative or the Home Office for further information.
Unit Oil Charging and Priming
WARNING
Avoid skin contact with oil. Wear rubber gloves and a face shield when working with oil. Failure to comply may result in serious injury or death.
Failure to follow these instructions will result in bearing damage and compressor seizing and will void any and all warranties that may apply.
Typically, the compressor unit is shipped from Vilter with no oil charge. The normal operating level is between the two sight glasses on the oil separator, see Figure
For regular oil charging and draining procedures, see Section 5.
Tool Required:
•Oil Pump, Maximum
(Reference Figure
1.At initial start up, compressor unit must be off and depressurized prior to initial oil charging.
2.Using a properly selected oil pump, connect oil pump to oil separator drain valve (4). For oil separa- tor drain valve location, see Figure
3.Open oil separator drain valve (4) and fill oil separa- tor (3) to Maximum
4.Once Maximum
5.If equipped with remote oil cooler, refer to Priming Remote Oil Cooler and Piping procedure.
PRIMING OIL COOLER (SHELL AND TUBE) AND PIPING
If equipped with a shell and tube oil cooler, continue with the following steps:
6.Close
7.Open oil bypass
8.Energize compressor unit.
9.Close oil mixing valve (oil temp. control valve) (7) via control panel. In Manual Mode, change “Manually Open (%)” value to “0”.
NOTE
The oil cooler is considered primed when the oil
level in the separator is constant.
10.Run the oil pump (6) twice for
3 – 16 | VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG |