Section 4 • Operation
Fail Position
The temperature control valve remains in the last posi- tion when power is removed.
Screen Display
The oil temperature control valve, identified as “OIL MIX” on the main PLC display screen, shows a numerical value with “%” as units. This is to be understood as “% OPEN.” It is a direct indication of the position of the ball valve.
100% OPEN
Oil flow stream is entirely bypassing the oil cooler.
99% to 1% OPEN
Oil flow stream is partially bypassing the oil cooler and partially diverted to the oil cooler.
0% OPEN
Oil flow stream is entirely diverted to the oil cooler.
Handwheel
Actuator
MANUAL OVERRIDE
The actuator of the oil temperature control valve has a handwheel that can be engaged to override the electri- cally determined position of the ball valve.
1.Push handwheel down and rotate to engage inter- nal slot with flats, see Figure
NOTE
Actuator does not have mechanical stops. Do Not rotate past open or close position. Use visual indicator to position actuator.
2.Once engaged, push down handwheel a second time to disengage gear train and rotate CLOCKWISE to OPEN or COUNTER CLOCKWISE to CLOSE.
3.To return actuator to normal operation, first check “% OPEN” on control panel. If value is 100%, return actuator to OPEN position as shown on the visual indicator. If value is 0%, return actuator to CLOSE position as shown on the visual indicator.
Visual Indicator
Figure
4 – 8 | VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG |