ANALOG OUTPUT ENABLE/DISABLE SUBMENU:

Press b

Press d

5)Scroll though the available selection until ENBL displays to use Analog Output Retransmission (output proportional to the input signal).

6)Display shows STRD stored message momentarily and then

advances to CURR or VoLT Submenu only if it was changed, otherwise press a to advance to CURR or VoLT Current/Voltage Submenu.

If DSBL Analog Output Disabled was selected, all submenus of Analog Output Menu will be skipped and the meter will advance to ALR2 Alarm 2 Menu. If ENBL Analog Output Enabled was selected, Output 1 would be automatically Disabled, and reassigned as Analog Output.

CURRENT/VOLTAGE SUBMENU:

Press d

Press b

Press d

READING 1:

7)Display flashes CURR Current or VoLT Voltage.

8)Scroll through the available selection: Current or Voltage (Example VoLT ).

9)Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed, otherwise press a to advance to RD1 Reading 1 Submenu.

Press d

Press b & c

Press d

OUT 1:

Press d

Press b & c

Press d

READING 2:

Press d

Press b & c

Press d

OUT 2:

Press d

Press b & c

Press d

10)Display flashes 1st digit of previous “Reading 1” value.

11)Enter “Reading 1” value. (Example 0000)

12)Display advances to OUT.1 Out 1 Submenu.

13)Display flashes 1st digit of previous “Out 1” value.

14)Enter “Out 1” value. (Example 00.00)

15)Display advances to RD!2 Reading 2 Submenu.

16)Display flashes 1st digit of previous “Reading 2” value.

17)Enter “Reading 2” value. (Example 9999)

18)Display advances to OUT.2 Out 2 Submenu.

19)Display flashes 1stt digit of previous “Out 2” value.

20)Enter “Out 2” value. (Example 10.00)

21)Display advances to the ALR2 Alarm 2 Menu.

The above example is for 0 - 10 V of the entire range of the Process Input and Analog Output. For 0 - 20 mA output you need to set “Analog Type” to Current and OUT 2 to 20.00.

31

Image 35
Contents CNiS8, CNiS8C CNiS8DH, CNiS8DV CNiS16, CNiS16D, CNiS32 Servicing North America Table of Contents List of Tables List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Rear Panel Connections Part SetupFront Panel Front Panel AnnunciatorsOption PowerInput OutputMain Power Connections Fuse Requirements Electrical Installation Power ConnectionsProcess Current Strain Gauge Figure below shows the wiring hookup for 4-wire bridge inputOutputs Wiring Hookup 11 Snubber Circuits Wiring HookupRS-232 Output Wiring Hookup b RS-485 Output Wiring Hookup Wiring OutputsJumper Connections Excitation OutputTop View Location of S2 on 1/8 DIN Compact Unit Turning your Controller On for the First Time Part Operation Configuration ModeFlow Chart for ID and Set Points Menu Menu ConfigurationID Number Menu Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Setpoint Set Points MenuInput Type Menu Configuration MenuEnter Configuration Menu Ratiometric Operation Submenu INPUT/READING Resolution SubmenuEnter Input Type Menu Input Type MenuButton Selection Submenu Reading Configuration MenuLinearization Points Submenu Enter Reading Configuration MenuDecimal Point Submenu KNOWN/UNKNOWN Loads SubmenuFilter Constant Submenu Example 1 Scaling with Known Loads On-Line Calibration Input/Reading Scale and Offset MenuExample 2 Scaling without Known Loads Input Resolution MultiplierConversion Table Page Page Enter Alarm 1 Menu Alarm 1 MenuAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Active Submenu Contact Closure SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Enter Analog Output Menu Analog Output Retransmission MenuOUT Analog Output ENABLE/DISABLE SubmenuCURRENT/VOLTAGE Submenu ReadingFor example Enter Alarm 2 Menu Alarm 2 MenuEnter Loop Break Time Menu Alarm 2 ENABLE/DISABLE SubmenuLoop Break Time Menu Loop Break Time Value Submenu Loop Break ENABLE/DISABLE SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Output 1 Menu Flow Chart for Output 1 MenuMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu Control Type Output MAXIMUM/PERCENT High SubmenuAnti Integral Submenu Action Type SubmenuAuto PID Submenu Proportional Band Submenu Start Auto Tune PIDCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Deadband Submenu Damping Factor SubmenuControl Type Submenu Output 2 MenuEnter Output 2 Menu Be called Reverse Acting Cycle Time Submenu Enter Ramp and Soak Menu Ramp ENABLE/DISABLE SubmenuRamp & Soak Menu Soak Value Submenu Soak ENABLE/DISABLE SubmenuRamp Value Submenu Enter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code Menu SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu Communication Option Menu 13 Flow Chart for Communication Option MenuParity Submenu Enter Communication Option MenuCommunication Parameters Submenu Baud SubmenuLine Feed Submenu Stop BIT SubmenuBUS Format Submenu Modbus Protocol SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Peak Value Submenu Alarm Status SubmenuData Format Submenu Main Reading SubmenuTransmit Time Interval Submenu Address Setup SubmenuUnit Submenu not applicable Address Value SubmenuNormal Color Display Submenu Alarm 1 Display Color SubmenuDisplay Color Selection Menu Enter Display Color Selection MenuGreen RED Amber Alarm 2 Display Color SubmenuExample Display Colors change sequencesAmber Green Control Part SpecificationsInsulation Control Output 1SSR ExcitationGeneral Factory preset value Part Factory Preset ValuesMenu Items Factory Preset Values PID Measurement Category Part CE Approvals InformationPage Page Return REQUESTS/INQUIRIES WARRANTY/DISCLAIMERData Acquisition TemperaturePRESSURE, Strain and Force FLOW/LEVEL