Omega CNiS8DH, CNiS32, CNiS16D, CNiS8DV, CNiS8C manual General

Page 65

Approvals

UL, C-UL and see CE Approval Section

GENERAL

Line Voltage/Power

90-240 Vac +/-10%, 50-400 Hz*

110-375 Vdc, equivalent voltage

4 W power for iS8, iS8C, iS16, iS32

5 W, power for iS8DV, iS8DH, iS16D

*No CE compliance above 60 Hz

Low Voltage/Power Option

12-36 Vdc, 3 W**power for iS8, iS8C, iS16, and iS32

20-36 Vdc, 4 W, power for iS8DV, iS8DH, and iS16D

External power source must meet Safety Agency Approvals.

**Units can be powered safely with 24 Vac power but, no Certification for CE/UL are claimed.

External Fuse Required Time-Delay, UL 248-14 listed:

100 mA/250 V

400 mA/250 V (Low Voltage/Power Option) Time-Lag, IEC 127-3 recognized:

100 mA/250 V

400 mA/250 V (Low Voltage/Power Option)

Environmental Conditions

•All models: 0 to 55 °C (32 to 131 °F), 90% RH non-condensing

•iS8DV, iS8DH, iS8C, iS16D:

0 to 50 °C (32 to 122 °F) for UL only, 90% RH non-condensing

Protection

NEMA-4x/Type 4x/IP65 front bezel: iS32, i1S6D, iS8C

NEMA-1/Type 1 front bezel: iS8, iS8DH, iS8DV

Dimensions i/8 Series:

48 H x 96 W x 127 mm D

(1.89 x 3.78 x 5")

i/8 Compact Series:

48 H x 96 W x 74 mm D

(1.89 x 3.78 x 2.91")

i/16 Series: 48 H x 48 W x 127 mm D (1.89 x 1.89 x 5")

i/32 Series:

25.4H x 48 W x 127 mm D

(1.0 x 1.89 x 5")

Panel Cutout i/8 Series:

45 H x 92 W mm (1.772" x 3.622 "), 1/8 DIN

i/16 Series: 1/16 DIN 45 mm (1.772") square

i/32 Series:

22.5H x 45 W mm (0.886" x 1.772"), 1/32 DIN

Weight

i/8 Series: 295 g (0.65 lb)

i/16 Series: 159 g (0.35 lb)

i/32 Series: 127 g (0.28 lb)

61

Image 65
Contents CNiS8, CNiS8C CNiS8DH, CNiS8DV CNiS16, CNiS16D, CNiS32 Servicing North America Table of Contents List of Tables List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Front Panel Part SetupFront Panel Annunciators Rear Panel ConnectionsInput PowerOutput OptionMain Power Connections Fuse Requirements Electrical Installation Power ConnectionsProcess Current Strain Gauge Figure below shows the wiring hookup for 4-wire bridge inputOutputs Wiring Hookup 11 Snubber Circuits Wiring HookupRS-232 Output Wiring Hookup b RS-485 Output Wiring Hookup Wiring OutputsJumper Connections Excitation OutputTop View Location of S2 on 1/8 DIN Compact Unit Turning your Controller On for the First Time Part Operation Configuration ModeFlow Chart for ID and Set Points Menu Menu ConfigurationID Number Menu Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Setpoint Set Points MenuInput Type Menu Configuration MenuEnter Configuration Menu Enter Input Type Menu INPUT/READING Resolution SubmenuInput Type Menu Ratiometric Operation SubmenuButton Selection Submenu Reading Configuration MenuDecimal Point Submenu Enter Reading Configuration MenuKNOWN/UNKNOWN Loads Submenu Linearization Points SubmenuFilter Constant Submenu Example 1 Scaling with Known Loads On-Line Calibration Input/Reading Scale and Offset MenuExample 2 Scaling without Known Loads Input Resolution MultiplierConversion Table Page Page Enter Alarm 1 Menu Alarm 1 MenuAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Active Submenu Contact Closure SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Enter Analog Output Menu Analog Output Retransmission MenuCURRENT/VOLTAGE Submenu Analog Output ENABLE/DISABLE SubmenuReading OUTFor example Enter Alarm 2 Menu Alarm 2 MenuEnter Loop Break Time Menu Alarm 2 ENABLE/DISABLE SubmenuLoop Break Time Menu Loop Break Time Value Submenu Loop Break ENABLE/DISABLE SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Output 1 Menu Flow Chart for Output 1 MenuMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu Control Type Output MAXIMUM/PERCENT High SubmenuAnti Integral Submenu Action Type SubmenuAuto PID Submenu Proportional Band Submenu Start Auto Tune PIDCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Deadband Submenu Damping Factor SubmenuControl Type Submenu Output 2 MenuEnter Output 2 Menu Be called Reverse Acting Cycle Time Submenu Enter Ramp and Soak Menu Ramp ENABLE/DISABLE SubmenuRamp & Soak Menu Soak Value Submenu Soak ENABLE/DISABLE SubmenuRamp Value Submenu Enter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code Menu SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu Communication Option Menu 13 Flow Chart for Communication Option MenuCommunication Parameters Submenu Enter Communication Option MenuBaud Submenu Parity SubmenuBUS Format Submenu Stop BIT SubmenuModbus Protocol Submenu Line Feed SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Data Format Submenu Alarm Status SubmenuMain Reading Submenu Peak Value SubmenuUnit Submenu not applicable Address Setup SubmenuAddress Value Submenu Transmit Time Interval SubmenuDisplay Color Selection Menu Alarm 1 Display Color SubmenuEnter Display Color Selection Menu Normal Color Display SubmenuExample Alarm 2 Display Color SubmenuDisplay Colors change sequences Green RED AmberAmber Green Control Part SpecificationsSSR Control Output 1Excitation InsulationGeneral Factory preset value Part Factory Preset ValuesMenu Items Factory Preset Values PID Measurement Category Part CE Approvals InformationPage Page Return REQUESTS/INQUIRIES WARRANTY/DISCLAIMERPRESSURE, Strain and Force TemperatureFLOW/LEVEL Data Acquisition