Omega CNiS8DH, CNiS32, CNiS16D, CNiS8DV, CNiS8C manual For example

Page 36

Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following conditions are satisfied:

1.The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @ 20 mA input ranges).

2.Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or 0.6 mA @ 20 mA output ranges).

Otherwise certain corrections need to be applied.

For example:

For entire range of process input, the Analog Output on 10 V FS scaled for

300 mV output range:

Rd1 = 0000, Out1 = 00.00

RD2 = 9999, Out2 = 00.30

The measured output will be as follows:

Rd1 = 0000, Out1 = -0.07 V

Rd2 = 9999, Out2 = 0.23 V

This means that for 300 mV output range we have -70 mV offset at zero and at full scale. In order to compensate this 70 mV offset the correct scaling will be as follows:

Rd1 = 0000, Out1 = 00.07

Rd2 = 9999, Out2 = 00.37

The above corrections need to be applied only for Input scaled below 1% of FS and Output scaled below 3% of FS or if you need the Analog Output accuracy to be better than 1% of FS.

32

Image 36
Contents CNiS8, CNiS8C CNiS8DH, CNiS8DV CNiS16, CNiS16D, CNiS32 Servicing North America Table of Contents List of Figures List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup Front PanelFront Panel Annunciators Rear Panel ConnectionsPower InputOutput OptionElectrical Installation Power Connections Main Power Connections Fuse RequirementsProcess Current Figure below shows the wiring hookup for 4-wire bridge input Strain Gauge11 Snubber Circuits Wiring Hookup Outputs Wiring HookupWiring Outputs RS-232 Output Wiring Hookup b RS-485 Output Wiring HookupExcitation Output Top View Location of S2 on 1/8 DIN Compact UnitJumper Connections Part Operation Configuration Mode Turning your Controller On for the First TimeMenu Configuration Flow Chart for ID and Set Points MenuEntering Your NON-DEFAULT Full Security ID Number Entering Your NON-DEFAULT SETPOINT/ID Security ID NumberID Number Menu Set Points Menu SetpointConfiguration Menu Enter Configuration MenuInput Type Menu INPUT/READING Resolution Submenu Enter Input Type MenuInput Type Menu Ratiometric Operation SubmenuReading Configuration Menu Button Selection SubmenuEnter Reading Configuration Menu Decimal Point SubmenuKNOWN/UNKNOWN Loads Submenu Linearization Points SubmenuFilter Constant Submenu Input/Reading Scale and Offset Menu Example 1 Scaling with Known Loads On-Line CalibrationInput Resolution Multiplier Conversion TableExample 2 Scaling without Known Loads Page Page Alarm 1 Menu Enter Alarm 1 MenuAlarm 1 ENABLE/DISABLE Submenu Alarm 1 ABSOLUTE/DEVIATION SubmenuAlarm 1 LATCH/UNLATCH Submenu Contact Closure Submenu Active SubmenuAlarm ENABLE/DISABLE AT Power on Alarm 1 LOW Value SubmenuAlarm 1 HI Value Submenu Analog Output Retransmission Menu Enter Analog Output MenuAnalog Output ENABLE/DISABLE Submenu CURRENT/VOLTAGE SubmenuReading OUTFor example Alarm 2 Menu Enter Alarm 2 MenuAlarm 2 ENABLE/DISABLE Submenu Loop Break Time MenuEnter Loop Break Time Menu Loop Break ENABLE/DISABLE Submenu Setpoint Deviation ENABLE/DISABLE SubmenuLoop Break Time Value Submenu Flow Chart for Output 1 Menu Output 1 MenuEnter Output 1 Menu Self SubmenuMINIMUM/PERCENT LOW Submenu MAXIMUM/PERCENT High Submenu Control Type OutputAction Type Submenu Auto PID SubmenuAnti Integral Submenu Start Auto Tune PID Proportional Band SubmenuReset Setup Submenu Rate Setup SubmenuCycle Time Submenu Damping Factor Submenu Deadband SubmenuOutput 2 Menu Enter Output 2 MenuControl Type Submenu Be called Reverse Acting Cycle Time Submenu Ramp ENABLE/DISABLE Submenu Ramp & Soak MenuEnter Ramp and Soak Menu Soak ENABLE/DISABLE Submenu Ramp Value SubmenuSoak Value Submenu Entering or Changing Your NON-DEFAULT ID Code ID Code MenuEnter ID Code Menu Entering or Changing Your Default ID Code Full Security Level SubmenuSETPOINT/ID Security Level Submenu 13 Flow Chart for Communication Option Menu Communication Option MenuEnter Communication Option Menu Communication Parameters SubmenuBaud Submenu Parity SubmenuStop BIT Submenu BUS Format SubmenuModbus Protocol Submenu Line Feed SubmenuData Flow Mode Submenu Communication Interface Standard SubmenuData Separation Character Submenu Alarm Status Submenu Data Format SubmenuMain Reading Submenu Peak Value SubmenuAddress Setup Submenu Unit Submenu not applicableAddress Value Submenu Transmit Time Interval SubmenuAlarm 1 Display Color Submenu Display Color Selection MenuEnter Display Color Selection Menu Normal Color Display SubmenuAlarm 2 Display Color Submenu ExampleDisplay Colors change sequences Green RED AmberAmber Green Part Specifications ControlControl Output 1 SSRExcitation InsulationGeneral Part Factory Preset Values Factory preset valueMenu Items Factory Preset Values PID Part CE Approvals Information Measurement CategoryPage Page WARRANTY/DISCLAIMER Return REQUESTS/INQUIRIESTemperature PRESSURE, Strain and ForceFLOW/LEVEL Data Acquisition