Soleus Air KFHHP-22 Parameters of temperature, Fundermental function of system, Cool mode

Page 10

Controller function of outdoor unit

6.1.1 Parameters of temperature

Exhausting gas temperature of outdoor unit(Tex)

Ambient temperature of outdoor unit(Tam)

6.1.2 Fundermental function of system

In wichever mode, once compressor start-up, it can only be close down 6 minutes later at least(not including malfunction protection/mode switch which requires compressor to stop);Once compressor closes down, it can only restart 3 minutes later at least(including mode switch, stop by remote control etc.);compressor starts up after outdoor motor runs for 5 seconds

6.1.2.1 Cool mode

6.1.2.1.1Working conditions and process of cooling

when compressor in closing down state and (Tin-am-Tset) 0.5 ,if unit start in cooling mode,

then cooling mode operates; outdoor fan motor and compressor start to run. The frequency of compressor can be adjusted automatically according to need of cooling power by micro-computer.

during cooling process, when 0

(Tset-Tin-am)

2 ,the compressor

operates in low

frequency.

 

 

 

during cooling process, when 0 need of cooling power and (Tset-Tin-am) 2

, then compressor

stops running. And outdoor fan motor stops in 60s.

In this mode, there is no power supply for reversing valve. Range of temperature setting is 16-30

.

6.1.2.1.2 Frost-proof protection

In cool and dehumidifying mode, when frost-proof protection is detected, the compressor will run in lower frequency or stops. And outdoor fan motor stops in 60s. When frost-proof protection ends, Compressor resumes running.

6.1.2.1.3 Controlling principles of outdoor fan motor

If Tout-am

26 , the fan motor runs in high speed.

If Tout-am

24 , the fan motor runs in low speed.

If 24

Tout-amb 26 , the fan motor runs in original speed.

After fan motor runs in compulsive high speed for 3 minutes in starting-up, then the speed will be controlled by the set principles

6.1.2.2 Dehumidifying mode

Working conditions and process of dehumidifying: the same with the ones in cooling mode

status of 4-way valve: closed

range of temperature setting: 16-30

protection function: the same with the ones in cooling mode.

6.1.2.3 Fan mode

compressor, outdoor fan motor and 4-way valve are closed and stopped. range of temperature setting: 16-30

6.1.2.4 Heating mode

6.1.2.4.1 Working conditions and process of heating

when compressor in closing down state and (Tin-amb-3)

(Tset-0.5)

, if unit start in heating

mode, then heating mode operates. Outdoor fan motor ,compressor and

4-way valve start to run.

The frequency of compressor can be adjusted automatically according to need of heating power by micro-computer.

-10-

Image 10
Contents Introduction and features Model RemarksSpecifications and technical parameters KFHHP-22KFHHP-22-OD Components name Indoor unit Outdoor unitOverall and installation dimension Overall and installation dimension of indoor unitOverall and installation dimension of outdoor unit NutGgggg KFHHP-22 Fundamental function Temperature parametersOther control Communication failure Dehumidifying mode Parameters of temperatureCool mode Fan modeCurrent protection function Overcurrent protection Time-delay protection of compressorHigh exhausting gas temp. protection of compressor Defrosting processCommunication failure Testing of malfunction of temp. sensor and IPM overheatingFrequency demultiplying, limitation of current control Module protectionStatus of indicator in outdoor unit D11D17 Disassemble filter Disassemble guide louverDisassemble electrical box cover Disassemble front caseDisassemble electrical box Disassemble water tray Disassemble evaporator assyDisassemble motor Disassemble cross flow fanDisassembly procedures for outdoor unit Operating procedures /picturesDisassemble housing case Disassemble 4-way valve Disassemble motor and motor supportOperating procedures/pictures Disassemblle capillaryExploded view and components&part list Indoor unitComponents and part list of indoor unit KFHHP-22-OD Components and part list of outdoor unit PCB JGP011Troubleshooting Replace the controller Change batteryPage Poor cooling heating effect Improper setting of temperature Wrap and tight it again Malfunction display section Rectifying bridge, reactor, capacitance etc. is ok