Soleus Air KFHHP-22 service manual Wrap and tight it again

Page 30

 

drain hose is blocked or broken

replace the drain hose

water leakage

 

 

 

connector of refrigerant pipe isn't wrapped well

wrap and tight it again

 

 

 

indoor fan collides with other parts

adjust the location of fan

 

abnormal things in indoor unit

remove it

 

 

 

compresoor shakes overly

adjust the washer and tight the bolt

 

 

abnormal shake

pipes in outdoor unit collides

set the pipes apart

 

 

or sound

 

 

 

metal plates collides

tighten the connecting bolt

 

 

 

 

stick shake-reduction plaster between the metal plates

 

outdoor fan collides with case

adjust the fan location

 

abnormal sound inside compressor

replace compressor

 

abnormal electromagnetic sound in

short circuit inside electromagnetic valve;repalace it

 

4-way valve in HEAT mode

 

 

CAUTION:

 

 

1,When repairing,before the voltage between module PN is measured below 50V,do not touch any terminal

to avoid electrical shock

 

2,When replacing power module and rectifier,make sure to spread the indicating paste evenly

 

-30-

 

Image 30
Contents Introduction and features Model RemarksSpecifications and technical parameters KFHHP-22KFHHP-22-OD Components name Indoor unit Outdoor unitOverall and installation dimension Overall and installation dimension of indoor unitOverall and installation dimension of outdoor unit NutGggggKFHHP-22 Temperature parameters Fundamental functionOther control Communication failure Dehumidifying mode Parameters of temperatureCool mode Fan modeCurrent protection function Overcurrent protection Time-delay protection of compressorHigh exhausting gas temp. protection of compressor Defrosting processCommunication failure Testing of malfunction of temp. sensor and IPM overheatingFrequency demultiplying, limitation of current control Module protectionStatus of indicator in outdoor unit D11D17 Disassemble filter Disassemble guide louverDisassemble front case Disassemble electrical box coverDisassemble electrical box Disassemble water tray Disassemble evaporator assyDisassemble motor Disassemble cross flow fanDisassembly procedures for outdoor unit Operating procedures /picturesDisassemble housing case Disassemble 4-way valve Disassemble motor and motor supportOperating procedures/pictures Disassemblle capillaryExploded view and components&part list Indoor unitComponents and part list of indoor unit KFHHP-22-OD Components and part list of outdoor unit PCB JGP011 Troubleshooting Replace the controller Change batteryPage Poor cooling heating effect Improper setting of temperature Wrap and tight it again Malfunction display section Rectifying bridge, reactor, capacitance etc. is ok