during heating process, when Tset | (Tset +2) ,the compressor operates | |
in low frequency. |
|
|
during heating process, when | (Tset +2) , then compressor stops running. And |
outdoor fan motor stops in 60s.
Notice: It will take 2 minutes to
In this mode, there is power supply for reversing valve. Range of temperature setting is
6.1.2.4.2 Controlling principles of outdoor fan motor
If | 19 | , the fan motor runs in high speed. | |
If | 21 | , the fan motor runs in low speed. | |
If 19 | 21 , the fan motor runs in original speed. |
After fan motor runs in compulsive high speed for 3 minutes in
6.1.2.4.3 Defrosting process
When defrosting conditions is detected, if compressor run in high frequency, then frequency will be demultiplied first. Later compressor stops running and indoor fan motor stops. Outdoor fan motor stops in 50s later.
If compressor closes down for malfunction in heating mode, indoor motor will only exhausting remaining heat.
6.1.3Universal protection function of cool, heating, dehumidifying and auto
mode
6.1.3.1 Overloading protection function
When
If there are 6 continuous times of
6.1.3.2 Time-delay protection of compressor
Compressor will restart in 3 minutes after it closes down.
6.1.3.3 High exhausting gas temp. protection of compressor
When
If there are 6 continuous times of
6.1.3.4Current protection function
(1) overcurrent protection
If current of whole unit is beyond max. limit, unit will close down as if indoor temperature reaches the set temperature. Unit will restore automatically after compressor has been stop for 3 minutes.