Soleus Air KFHHP-22 service manual Rectifying bridge, reactor, capacitance etc. is ok

Page 32

7.Module protection : Handling method:

Check if the voltage between power module P and N is too low and if the current is too high. In normal condition, voltage between P and N should be about 320V.

 

 

 

 

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

Check power supply circuit of outdoor unit (if PTCresistance

 

 

 

 

rectifying bridge, reactor, capacitance etc. is ok).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if radiating paste is spread

 

 

Reinstall power module and

 

 

 

 

 

 

 

 

 

evenly or radiating sticker is stuck

 

 

re-spread radiating paste or

Temperature of power module is too high,

 

 

 

 

 

 

well; if screws of power module

 

 

 

 

which causes overheating protection

 

 

 

 

stick radiating sticker on the

 

 

 

 

is tightened

 

 

radiator of power module.

 

Protection is still displayed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Confirm the setting status of outdoor unit (cooling)

Normal

Poor radiation, heat exchanger is dirty

Remove obstructions and clean

Confirm if outdoor fan motor is running; unplug the

three connecting wires between U, V, W of compressor and power module. Turn on the unit to see if outdoor

fan runs normally (about 1 minute)

Outdoor fan runs

Confirm if there is voltage output and balance of voltage between any two phases of U, V and W.

Outdoor fan stops

Measure the voltage of outdoor fan connector

No voltage

Normal voltage

 

Replacethemainboard

 

Replace the fan

of outdoor unit

 

motor

 

 

 

 

 

 

Yes

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

Whether module type

 

 

Replacethepowermodule

 

is correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Abnormal

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the module

 

Measure the three-phase

 

 

with correct type

 

resistance of compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

Whether cylinder of compressor is stuck

Abnormal

Replace the compressor

If the unit runs normally after connected

with the new compressor for trial run, the cylinder of original compressor is stuck

32

Image 32
Contents Introduction and features Model RemarksSpecifications and technical parameters KFHHP-22KFHHP-22-OD Components name Indoor unit Outdoor unitOverall and installation dimension Overall and installation dimension of indoor unitOverall and installation dimension of outdoor unit NutGggggKFHHP-22 Other control Temperature parametersFundamental function Communication failure Parameters of temperature Cool modeDehumidifying mode Fan modeTime-delay protection of compressor High exhausting gas temp. protection of compressorCurrent protection function Overcurrent protection Defrosting processTesting of malfunction of temp. sensor and IPM overheating Frequency demultiplying, limitation of current controlCommunication failure Module protectionStatus of indicator in outdoor unit D11D17 Disassemble filter Disassemble guide louverDisassemble electrical box Disassemble front caseDisassemble electrical box cover Disassemble water tray Disassemble evaporator assyDisassemble motor Disassemble cross flow fanDisassembly procedures for outdoor unit Operating procedures /picturesDisassemble housing case Disassemble 4-way valve Disassemble motor and motor supportOperating procedures/pictures Disassemblle capillaryExploded view and components&part list Indoor unitComponents and part list of indoor unit KFHHP-22-OD Components and part list of outdoor unit PCB JGP011Troubleshooting Replace the controller Change batteryPage Poor cooling heating effect Improper setting of temperature Wrap and tight it again Malfunction display section Rectifying bridge, reactor, capacitance etc. is ok