Soleus Air KFHHP-22 service manual Poor cooling heating effect Improper setting of temperature

Page 29

Poor cooling (heating) effect

Improper setting of temperature

Adjust the set temperature

 

 

Whether cooling (heating) load

Check the estimated load of cooling (heating)

is proper

 

 

 

 

 

 

 

Vacuumize

after leakage detection

 

Leakage or shortage of refrigerant

and leakage repair. Charge refrigerant

 

 

 

according to specification.

 

Leakage occurs between high and

Replace the compressor

 

low pressure inside compressor

 

 

Malfunction of

Malfunction of four-way valve

Replace the four-way valve

refrigerant flow

 

Partial blockage of capillary

Replace the capillary

 

 

 

Use the method of observing condensation

 

Blockage of cooling system

on the evaporator and pressure value of

 

high pressure

manometer to see whether

the system is blocked and carry out corresponding handling on the system

Poor thermal insulation of connecting

Ensure that both thick pipe and thin pipe are insulated

well. The exposed part of the connector and copper pipe

pipe of indoor and outdoor unit

must be insulated as well.

 

Air circulation is insufficient

Heat exchanger of outdoor unit is blocked

Air filters are blocked

Fan speed is set too slow

Fan speed turns low

Improper installation location for outdoor unit

Clean the dust accumulated on the surface of the heat exchanger

Clean the filter

Set the fan speed to high or medium speed

Damage of

Replace

the

capacitor

capacitor

 

damaged

 

 

Damage of

Replace the motor

motor

 

 

Outdoor unit should be installed in a place with well ventilation

Outdoor temperature is too high

Indoor sealability is inadequate; too many people go in and out frequently; there is heating unit in the room.

Flashing or awning can be installed appropriately. If the max. cooling capacity cannot be satisfied, replacement of the air conditioner is recommended.

Maintain a certain degree of indoor sealability. Try not to use appliance with high amount of heat.

29

Image 29
Contents Model Remarks Introduction and featuresKFHHP-22 Specifications and technical parametersKFHHP-22-OD Outdoor unit Components name Indoor unitOverall and installation dimension of indoor unit Overall and installation dimensionNutGgggg Overall and installation dimension of outdoor unitKFHHP-22 Other control Temperature parametersFundamental function Communication failure Cool mode Parameters of temperatureDehumidifying mode Fan modeHigh exhausting gas temp. protection of compressor Time-delay protection of compressorCurrent protection function Overcurrent protection Defrosting processFrequency demultiplying, limitation of current control Testing of malfunction of temp. sensor and IPM overheatingCommunication failure Module protectionD11 Status of indicator in outdoor unitD17 Disassemble guide louver Disassemble filterDisassemble electrical box Disassemble front caseDisassemble electrical box cover Disassemble evaporator assy Disassemble water trayDisassemble cross flow fan Disassemble motorOperating procedures /pictures Disassembly procedures for outdoor unitDisassemble housing case Disassemble motor and motor support Disassemble 4-way valveDisassemblle capillary Operating procedures/picturesIndoor unit Exploded view and components&part listComponents and part list of indoor unit KFHHP-22-OD PCB JGP011 Components and part list of outdoor unitReplace the controller Change battery TroubleshootingPage Poor cooling heating effect Improper setting of temperature Wrap and tight it again Malfunction display section Rectifying bridge, reactor, capacitance etc. is ok