Soleus Air KFHHP-22 service manual Troubleshooting, Replace the controller Change battery

Page 27

9Troubleshooting

Analysis in this section is used for D.C. Variable Frequency Series. Before analysis, you can diagnose according to the code displayed on indoor unit or indicator display on outdoor unit. (Refer to Malfunction display section).

Breaker tripped or fuse burnt out

 

Air

conditioner

 

does

not response

Air

after

powered on.

(The

buzzer

does

conditi

not sound after the

oner

plug

is

connected

and

the

unit

does

cannot

not response

after

start up

the

 

remote

 

controller is

used

 

to turn it on)

 

 

 

 

 

 

Remote controller does not receive signal (When powered on, the buzzer will send out a sound, unless it is broken)

When the breaker is set ON, it will trip at once

When the unit is turned on, the breaker will trip in a few minutes

No power supply

The power plug is not or poorly connected

Controller fuse is burnt out

Loose or poor contact of transformer connection, or transformer malfunction

The controller is broken

Batteries of remote controller are low

Malfunction of remote controller

Loose or poor connection of receiving head

Receiving head is broken

Measure the insulating resistance for grounding to confirm whether there is electrical leakage or short circuit in the unit

Insulation malfunction of line or componen in the air conditioner. Insulation breakdow occurs after radiation, which causes shor circuit or electricity leakage. Measure insulating resistance or use one-by-on elimination method;

Malfunction of fuse. Replace it.

Check power supply circuit

Check and plug well plug, make loosen contact firm

Change control fuse

Secure the wire connection: measure the output voltage of the transformer and replace it if the value is wrong

Replace the controller

Change battery

First press the "AUTO" button of the manual switch. If there is no response, check according to the above method; if it is normal after the button is pressed, check if the installation location and wire connection of the receiving head are correct. If correct, replace the receiving head, or the remote controller.

-27-

Image 27
Contents Model Remarks Introduction and featuresKFHHP-22 Specifications and technical parametersKFHHP-22-OD Outdoor unit Components name Indoor unitOverall and installation dimension of indoor unit Overall and installation dimensionNutGgggg Overall and installation dimension of outdoor unitKFHHP-22 Temperature parameters Fundamental functionOther control Communication failure Fan mode Parameters of temperatureCool mode Dehumidifying modeDefrosting process Time-delay protection of compressorHigh exhausting gas temp. protection of compressor Current protection function Overcurrent protectionModule protection Testing of malfunction of temp. sensor and IPM overheatingFrequency demultiplying, limitation of current control Communication failureD11 Status of indicator in outdoor unitD17 Disassemble guide louver Disassemble filterDisassemble front case Disassemble electrical box coverDisassemble electrical box Disassemble evaporator assy Disassemble water trayDisassemble cross flow fan Disassemble motorOperating procedures /pictures Disassembly procedures for outdoor unitDisassemble housing case Disassemble motor and motor support Disassemble 4-way valveDisassemblle capillary Operating procedures/picturesIndoor unit Exploded view and components&part listComponents and part list of indoor unit KFHHP-22-OD PCB JGP011 Components and part list of outdoor unitReplace the controller Change battery TroubleshootingPage Poor cooling heating effect Improper setting of temperature Wrap and tight it again Malfunction display section Rectifying bridge, reactor, capacitance etc. is ok