Schneider Electric ATV61 manual Communication via Profibus DP network, Address, 1234

Page 45

3. Implementation of the communication option cards

3. 5. Communication via Profibus DP network

3. 5. 1. Reminder of the possible connection methods: Same as existing

3

= Rx/Tx-

6

= VP

5

= GND

8

= Rx/Tx+

3. 5. 2. Configuring the drive address on the Profibus DP network

With the Altivar 38’s VW3-A58307 Profibus DP option card, the drive address was coded via the programming terminal. You need, therefore, to use this terminal to find this address before turning off the drive and replacing it.

Transfer the Altivar 38 address to the Altivar 61 using the 7 switches on the right of the card; the value 0 being the OFF position, the value 1 the ON position.

Example

Address 23

Address 89

Address

Switches

 

1234 5678

01000 0000

11000 0001

21000 0010

31000 0011

41000 0100

51000 0101

61000 0110

71000 0111

81000 1000

91000 1001

101000 1010

111000 1011

121000 1100

131000 1101

141000 1110

151000 1111

161001 0000

171001 0001

181001 0010

191001 0011

201001 0100

211001 0101

221001 0110

231001 0111

241001 1000

251001 1001

261001 1010

271001 1011

281001 1100

291001 1101

301001 1110

311001 1111

Address

Switches

 

1234 5678

321010 0000

331010 0001

341010 0010

351010 0011

361010 0100

371010 0101

381010 0110

391010 0111

401010 1000

411010 1001

421010 1010

431010 1011

441010 1100

451010 1101

461010 1110

471010 1111

481011 0000

491011 0001

501011 0010

511011 0011

521011 0100

531011 0101

541011 0110

551011 0111

561011 1000

571011 1001

581011 1010

591011 1011

601011 1100

611011 1101

621011 1110

631011 1111

Address

Switches

 

1234 5678

641100 0000

651100 0001

661100 0010

671100 0011

681100 0100

691100 0101

701100 0110

711100 0111

721100 1000

731100 1001

741100 1010

751100 1011

761100 1100

771100 1101

781100 1110

791100 1111

801101 0000

811101 0001

821101 0010

831101 0011

841101 0100

851101 0101

861101 0110

871101 0111

881101 1000

891101 1001

901101 1010

911101 1011

921101 1100

931101 1101

941101 1110

951101 1111

Address

Switches

 

1234 5678

96

1110 0000

97

1110 0001

98

1110 0010

99

1110 0011

100

1110 0100

101

1110 0101

102

1110 0110

103

1110 0111

104

1110 1000

105

1110 1001

106

1110 1010

107

1110 1011

108

1110 1100

109

1110 1101

110

1110 1110

111

1110 1111

112

1111 0000

113

1111 0001

114

1111 0010

115

1111 0011

116

1111 0100

117

1111 0101

118

1111 0110

119

1111 0111

120

1111 1000

121

1111 1001

122

1111 1010

123

1111 1011

124

1111 1100

125

1111 1101

126

0111 1110

If the PLC module was configured using the Sycon < v2.8 configuration tool, it was possible to use address 126 for a subscriber (Altivar or other).

This address is reserved and, therefore, its use is prohibited from version v2.8 onwards in accordance with the recommendations of the Profibus consortium.

45

Image 45
Contents Altivar Variable-torque applications Table of contents Migration from ATV 38V ATV Altivar 38 hardware identification Choosing the Altivar 61 catalog number ATV38 catalog Power NumberYour catalog number starts with ATV38H Your catalog number starts with ATV38EDSelecting the power circuit options Removable power terminal kit VW3A5881x Mounting accessoriesAir exchanger kit VW3A5880x Nema type 1 mounting kitControl circuit options Separate control card power supply kit VW3A5860xControl card fan kit VW3A5882x Remote display terminal VW3A58103ATV38 and I/O option cards VW3A58201, VW3A58202 Selecting I/O extension cards VW3A58201, VW3A58202ATV38 PTCBecomes ATV PI feedback or summed reference Three different optionsVW3A58202 VW3... cardCommunication via Modbus network Selecting communication channelsCommunication with Profibus bus VW3A58307 Communication with DeviceNet bus VW3A58309Communication with Interbus bus VW3A58304E Communication with Metasys N2 bus VW3A58354UCommunication via Ethernet network VW3A58310 Communication via Fipio bus VW3A58311Using catalog numbers starting with ATV38H InstallationATV 61H075N4 Comparison of dimensions Width Height DepthATV 61HU15N4 ATV 61HU22N4ATV 61HD55N4 ATV 61HD45N4ATV 61HD75N4 ATV 61HD90N4Dimensions Comparison of dimensionsATV38Hppp product on heatsink ATV 61HD22N4 D15N4, D18N4D30N4, D37N4 D45N4, D55N4, D75N4ATV61H ATV 38Hppp 75 kW and y 315 kW Product on heatsinkDrive Filter Width Height Depth Mounting Mounting the RFI filterWidth Height Depth Mounting DriveComparison of dimensions RFI filtersVW3 Side mounting against the ATV Mounting under the driveKit catalog Nema mounting kitsATV38Hppppp Kit catalog ProductKit for UL Nema Type 1 conformity or IP 21 protection Remote display terminal Separate control card power supplyDisconnecting the RFI filter if using an IT system Power cablesLayout of the ATV38 power terminals Connecting to the AltivarAWG Characteristics of the ATV38 power terminalsDrive terminals L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 Maximum terminal wire size/tightening torquePC/-, PO, PA/+ PA, PBPA, PB RO, SO, to ATV61H D90M3X, C13N4ATV61HC16N4 ATV61HC22N4 ATV61H C25N4, C31N4 Control wiring and I/O characteristics Control and option card logic input wiringATV38 value kOhms LI6 wired as PTC probe Encoder General Installing the communication option cardAcceptance Check that the drive is turned offValue Description of parameter values Option card faultSchematic diagram Mixed schematicCommunication via Modbus network Calculating the polarization resistorsConfiguring the address Configuring the driveConfiguring the drive control mode Reminder of the various connection methodsPLC configuration and application Configuring communication monitoring Reminder of possible connection methods Address ATV38 switches ATV61 switches 12345678PLC configuration and application Configuring polarity on the drive RS 485 busCommunication via CANopen network Matching the line termination resistorAddress and Baud rate Configuring the driveCommunication via Profibus DP network Configuring the drive address on the Profibus DP networkAddress 1234Communication fault Configuring the drive in ATV38 Interchangeability modeConfiguring the drive address on the Fipio network Connecting to the Fipio busCommunication via Fipio network VW3 A3 311 option card PresentationManaging loss of Fipio communication Altivar 38 PKW indexed periodic variablesFamily Base moduleCommunication via Interbus network Configuring the communication parametersConfiguring the drive address on the Modbus Plus network Communication via Modbus Plus networkATV38 ATV61 Communication fault Configuring the drive address on the DeviceNet network Configuring the drive on the networkCommunication via DeviceNet network MACPLC configuration and application Drive implementation on the DeviceNet network Implementation of the communication option cards Implementation of the communication option cards Implementation of the communication option cards Implementation of the communication option cards P06 P06 Communication fault Using the Bootp protocol Drive configuration in Expert modeCommunication via Ethernet network Transmission speedFaulty Device Replacement FDR Using the DHCP-FDR protocolActivating the service Procedure on the AltivarProgramming the Altivar 38 Ethernet parameters Modbus serviceAvailable address fields XxxxEthernet card access to the Modbus server IO Scanning serviceConfiguring the periodic parameter assignment table Modbus functions availableFDR service fault EPF2 Configuring the IO Scanner page from the Http server Implementation of the communication option cards Altivar 38 PKW parameter-setting service Configuring the IO Scanner page using TCP/Modbus messagingSnmp agent Description ATV61 registerCommunication fault PDA Altivar page Last Fault = ILF FaultFDR service fault EPF2 Standard Http serverAS-i Assignment of the Inputs/Outputs 11 . +/- speed modeSpeed mode, 1 direction of operation Assignment of inputs/outputsSpeed mode, 2 directions of operation Configuring the drive logic I/OManaging the terminal outputs AS-i monitoring bits LimitationsPump card Application-specific option cardsMulti-motor card Multi-parameter cardAtv61migrationenv1 2006-04