3. Implementation of the communication option cards

3. 10. 10. Communication fault

Ethernet communication faults are indicated by the red FLT LED on the card.

Parameter [Network fault] (CnF-)can be used to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-)menu, [MORE FAULT INFO] (AFI-).

Value Description of the values of the [Network fault] (CnF-)parameter

0No fault

Tcp/Modbus Time out fault.

The Tcp/Modbus Time out is activated as soon as the control word is received:

1- If no IP master has been configured, the period of activity is maintained by receipt of the control word.

- If an IP master has been configured, the period of activity is maintained by any type of Tcp/Modbus request on this IP address.

No Time out is managed if its value equals 0.

10Ethernet network overload

11No signal from the Ethernet network, cable pulled out, etc.

3.10. 11. FDR service fault (EPF2)

The EPF2 communication fault is indicated by the red RD LED on the card.

This fault appears when a problem arises during the FDR status diagram sequence on the drive, provided that the FDR service is being used and that FDR errors are permitted on the drive ([FDR Error Mgt.] (FdrG) = [Yes] (YES) or FDR file error (address 60 060) = [Yes] (YES)). This fault is resettable.

The EPF2 fault is also triggered if the drive IP address is already being used by another device. In this case, the EPF2 fault is not resettable. You should then modify the drive IP address, or that of the device using this IP address, then restart the drive.

It is possible to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display

terminal, in the [1.9 COMMUNICATION] (COM-)menu, [Ethernet] (EtH-),[FDR fault] (Fdrd).

Value Description of the values of the [Network fault] (CnF-)parameter

2FDR configuration file incompatible

3Error reading the FDR file

4Error writing the FDR file

7Time out for access to the FTP server has elapsed. This time out cannot be set (90 s)

9Duplication of the IP address

12

FDR file not present in the FTP server

65

Image 65
Contents Altivar Variable-torque applications Table of contents Migration from ATV 38V ATV Altivar 38 hardware identification Choosing the Altivar 61 catalog number ATV38 catalog Power NumberYour catalog number starts with ATV38H Your catalog number starts with ATV38EDSelecting the power circuit options Removable power terminal kit VW3A5881x Mounting accessoriesAir exchanger kit VW3A5880x Nema type 1 mounting kitControl circuit options Separate control card power supply kit VW3A5860xControl card fan kit VW3A5882x Remote display terminal VW3A58103ATV38 and I/O option cards VW3A58201, VW3A58202 Selecting I/O extension cards VW3A58201, VW3A58202ATV38 PTCBecomes ATV PI feedback or summed reference Three different optionsVW3A58202 VW3... cardCommunication via Modbus network Selecting communication channelsCommunication with Profibus bus VW3A58307 Communication with DeviceNet bus VW3A58309Communication with Interbus bus VW3A58304E Communication with Metasys N2 bus VW3A58354UCommunication via Ethernet network VW3A58310 Communication via Fipio bus VW3A58311Using catalog numbers starting with ATV38H InstallationATV 61H075N4 Comparison of dimensions Width Height DepthATV 61HU15N4 ATV 61HU22N4ATV 61HD55N4 ATV 61HD45N4ATV 61HD75N4 ATV 61HD90N4Dimensions Comparison of dimensionsATV38Hppp product on heatsink ATV 61HD22N4 D15N4, D18N4D30N4, D37N4 D45N4, D55N4, D75N4ATV61H ATV 38Hppp 75 kW and y 315 kW Product on heatsinkDrive Filter Width Height Depth Mounting Mounting the RFI filterWidth Height Depth Mounting DriveVW3 Comparison of dimensionsRFI filters Side mounting against the ATV Mounting under the driveKit catalog Nema mounting kitsATV38Hppppp Kit catalog ProductKit for UL Nema Type 1 conformity or IP 21 protection Remote display terminal Separate control card power supplyDisconnecting the RFI filter if using an IT system Power cablesLayout of the ATV38 power terminals Connecting to the AltivarAWG Characteristics of the ATV38 power terminalsDrive terminals L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 Maximum terminal wire size/tightening torquePC/-, PO, PA/+ PA, PBPA, PB RO, SO, to ATV61H D90M3X, C13N4ATV61HC16N4 ATV61HC22N4 ATV61H C25N4, C31N4 ATV38 value kOhms Control wiring and I/O characteristicsControl and option card logic input wiring LI6 wired as PTC probe Encoder General Installing the communication option cardAcceptance Check that the drive is turned offValue Description of parameter values Option card faultSchematic diagram Mixed schematicCommunication via Modbus network Calculating the polarization resistorsConfiguring the address Configuring the driveConfiguring the drive control mode Reminder of the various connection methodsPLC configuration and application Configuring communication monitoringReminder of possible connection methods Address ATV38 switches ATV61 switches 12345678PLC configuration and application Configuring polarity on the drive RS 485 busCommunication via CANopen network Matching the line termination resistorAddress and Baud rate Configuring the driveCommunication via Profibus DP network Configuring the drive address on the Profibus DP networkAddress 1234Communication fault Configuring the drive in ATV38 Interchangeability modeConfiguring the drive address on the Fipio network Connecting to the Fipio busCommunication via Fipio network VW3 A3 311 option card PresentationManaging loss of Fipio communication Altivar 38 PKW indexed periodic variablesFamily Base moduleCommunication via Interbus network Configuring the communication parametersATV38 ATV61 Configuring the drive address on the Modbus Plus networkCommunication via Modbus Plus network Communication fault Configuring the drive address on the DeviceNet network Configuring the drive on the networkCommunication via DeviceNet network MACPLC configuration and application Drive implementation on the DeviceNet network Implementation of the communication option cards Implementation of the communication option cards Implementation of the communication option cards Implementation of the communication option cards P06 P06 Communication fault Using the Bootp protocol Drive configuration in Expert modeCommunication via Ethernet network Transmission speedFaulty Device Replacement FDR Using the DHCP-FDR protocolActivating the service Procedure on the AltivarProgramming the Altivar 38 Ethernet parameters Modbus serviceAvailable address fields XxxxEthernet card access to the Modbus server IO Scanning serviceConfiguring the periodic parameter assignment table Modbus functions availableFDR service fault EPF2 Configuring the IO Scanner page from the Http server Implementation of the communication option cards Altivar 38 PKW parameter-setting service Configuring the IO Scanner page using TCP/Modbus messagingSnmp agent Description ATV61 registerCommunication fault PDA Altivar page Last Fault = ILF FaultFDR service fault EPF2 Standard Http serverAS-i Assignment of the Inputs/Outputs 11 . +/- speed modeSpeed mode, 1 direction of operation Assignment of inputs/outputsSpeed mode, 2 directions of operation Configuring the drive logic I/OManaging the terminal outputs AS-i monitoring bits LimitationsPump card Application-specific option cardsMulti-motor card Multi-parameter cardAtv61migrationenv1 2006-04