Carrier R-410A manual Electrical Data, Standard Motors, Electrical Data, Alternate Motors

Page 18

Table 4 — Electrical Data, Standard Motors

UNIT

V-PH-Hz

VOLTAGE

FAN MOTOR

 

POWER SUPPLY

LIMITS

Hp (kW)

 

FLA

Minimum

MOCP

 

 

 

 

 

 

Circuit Amps

 

40RUA*25

208/230-3-60

187-253

5.0 (3.73)

 

14.6/12.8

18.3/16.0

30/25

 

 

 

 

 

 

 

460-3-60

414-506

5.0 (3.73)

 

6.4

8.0

15

40RUS*25

 

 

 

 

 

 

 

 

 

575-3-60

518-632

5.0 (3.73)

 

5.1

6.4

15

 

 

 

 

 

 

 

 

40RUA*28

208/230-3-60

187-253

7.5 (5.59)

 

21.4/19.4

26.9/24.3

45/40

 

 

 

 

 

 

 

460-3-60

414-506

7.5 (5.59)

 

9.7

12.1

20

40RUS*28

 

 

 

 

 

 

 

 

 

575-3-60

518-632

7.5 (5.59)

 

7.8

9.8

15

 

 

 

 

 

 

 

 

40RUA*30

208/230-3-60

187-253

10.0 (7.46)

 

28.2/26.8

35.3/33.5

60/60

 

 

 

 

 

 

 

460-3-60

414-506

10.0 (7.46)

 

13.4

16.8

30

40RUS*30

 

 

 

 

 

 

 

 

 

575-3-60

518-632

10.0 (7.46)

 

10.3

12.9

20

 

 

 

 

 

 

 

 

See Legend and Notes below.

Table 5 — Electrical Data, Alternate Motors

UNIT

V-PH-Hz

VOLTAGE

FAN MOTOR

 

POWER SUPPLY

LIMITS

Hp (kW)

 

FLA

Minimum

MOCP

 

 

 

 

 

 

Circuit Amps

 

40RUA*25

208/230-3-60

187-253

7.5 (5.59)

 

21.4/19.4

26.9/24.3

45/40

 

 

 

 

 

 

 

460-3-60

414-506

7.5 (5.59)

 

9.7

12.1

20

40RUS*25

 

 

 

 

 

 

 

 

 

575-3-60

518-632

7.5 (5.59)

 

7.8

9.8

15

 

 

 

 

 

 

 

 

40RUA*28

208/230-3-60

187-253

10.0 (7.46)

 

28.2/26.8

35.3/33.5

60/60

40RUA*30

460-3-60

414-506

10.0 (7.46)

 

13.4

16.8

30

40RUS*28

 

 

 

 

 

 

 

 

40RUS*30

575-3-60

518-632

10.0 (7.46)

 

10.3

12.9

20

 

 

 

 

 

 

 

 

See Legend and Notes below.

Legend and Notes For Tables 4 and 5

LEGEND

FLA

Full Load Amps

MOCP Maximum Overcurrent Protection

Motors are designed for satisfactory operation within 10% of nominal

voltages shown. Voltages should not exceed the limits shown in the

Determine maximum deviation from average voltage

(AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v

(AC) 397 – 396 = 1 v

Maximum deviation is 6 v.

Determine percent voltage imbalance.

Voltage Limits column.

% Voltage Imbalance = 100 x

6

NOTES:

1.Minimum circuit amps (MCA) and MOCP values are calculated in accor- dance with NEC (National Electrical Code), Article 440.

2.Motor FLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 1995.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v

BC = 403 v

AC = 396 v

393 + 403 + 396

Average Voltage =

3

1192

=

3 = 397

397

= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

18

Image 18
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Dimensions Size Unit Unit WeightDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units Chilled Water Coil 40RUS Physical Data, English Chilled Water UnitsUnit 40RUS Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsFitting Requirement Upper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 LTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Wiring Fan Contactor Coil Data Unit Voltage Maximum HoldingLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIMotor Drive Standard Drive Data, 60 Hz EnglishMedium-Static Drive Data, 60 Hz English FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure DropPreliminary Information Check Voltage Imbalance Comp A1 Comp B1