Carrier R-410A manual High-Static Drive Data, 60 Hz English, Standard Drive Data, 60 Hz SI

Page 28

Table 9C — High-Static Drive Data, 60 Hz — English

UNIT

40RUA*25

40RUA*28

40RUA*30

40RUS*25

40RUS*28

40RUS*30

 

MOTOR DRIVE

 

 

 

Motor Pulley Pitch Diameter (in.)

4.3-5.3

4.3-5.3

4.3-5.3

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

FAN DRIVE

 

 

 

Pulley Pitch Dia (in.)

7.4

8.6

8.6

Pulley Bore (in.)

17/16

115/16

115/16

Belt No. — Section

2—B

2—B

2—B

Belt Pitch (in.)

36.8

378

37.8

FAN SPEEDS (rpm)

 

 

 

Factory Setting

1118

1024

1024

Range

1014-

873-

873-

1200

1075

1075

 

Max Allowable Speed (rpm)

1200

1100

1100

Change per 1/2 Turn of

19.4

16.7

16.7

Moveable Motor Pulley

Flange

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

SHAFTS CENTER DISTANCE (in.)

8.16-

6.67-

6.67-

10.02

9.43

9.43

 

It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

Table 9D — Standard Drive Data, 60 Hz — SI

UNIT

40RUA*25

40RUA*28

40RUA*30

40RUS*25

40RUS*28

40RUS*30

 

MOTOR DRIVE

 

 

 

Motor Pulley Pitch Diameter (mm)

94.0-

109.2-

109.2-

119.4

134.6

134.6

 

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

FAN DRIVE

 

 

 

Pulley Pitch Dia (mm)

239

279

279

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

2—B

2—B

2—B

Belt Pitch (mm)

1062

(2) 1987

(2) 1987

(2) 1113

(2) 1113

 

 

FAN SPEEDS (r/s)

 

 

 

Factory Setting

12.9

12.5

12.5

Range

11.3-14.4

11.4-14.0

11.2-13.9

Max Allowable Speed (r/s)

20.0

18.3

18.3

Change per 1/2Turn of

0.255

0.218

0.218

Moveable Motor Pulley

Flange

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

SHAFTS CENTER DISTANCE (mm)

232-279

169-240

169-240

Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.

28

Image 28
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Dimensions Size Unit Unit WeightDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units 40RUS Physical Data, English Chilled Water Units Unit 40RUSChilled Water Coil Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsFitting Requirement Upper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 LTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Wiring Fan Contactor Coil Data Unit Voltage Maximum HoldingLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishMotor Drive FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure DropPreliminary Information Check Voltage Imbalance Comp A1 Comp B1