Carrier R-410A manual U a a 2 5 a 6 0 a 0 a

Page 9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

4 0 R U A A 2 5 A

1 A 6 – 0 A 0 A 0

_____________ ____

Model Type

40RU = Carrier Fan Coil

Puronr R---410A Refrigerant

Type of Coil

A = Standard DX Coil

S = Chilled Water Coil

Refrigerant Options

A = None

B = Steam Coil

C = Hot Water Coil

Nominal Tonnage

25 = 20 Tons

28 = 25 Tons

30 = 30 Tons

Not Used

A = Place Holder

Indoor Fan Options

1 = Fan Drive and Motor - Low / Motor Efficiency - Standard 2 = Fan Drive and Motor - Med / Motor Efficiency - Standard 3 = Fan Drive and Motor - High / Motor Efficiency - Standard 4 = Fan Drive and Motor - Low / Motor Efficiency - Premium 5 = Fan Drive and Motor - Med / Motor Efficiency - Premium 6 = Fan Drive and Motor - High / Motor Efficiency - Premium

Brand / Packaging

0 = Standard

Not Used

A = Place Holder

Service Options

0= Non-Painted Cabinet

1= Painted Cabinet

Not Used

A = Place Holder

Not Used

0 = Place Holder

Design Rev

--- = Catalog Model Number

Voltage

1 = 575/3/60

5 = 208/230/3/60

6 = 460/3/60

Coil Options

A = Al/Cu

Fig. 3 — Model Number Nomenclature

POSITION NUMBER

 

1

 

2

3

4

 

5

 

6

 

7

 

8

9

10

TYPICAL

 

4

 

8

0

8

 

G

 

1

 

2

 

3

4

5

 

POSITION

 

 

 

 

 

DESIGNATES

 

 

 

 

 

 

 

1−2

 

 

 

Week of manufacture (fiscal calendar)

 

 

 

 

 

3−4

 

 

 

Year of manufacture (”08” = 2008)

 

 

 

 

5

 

 

 

Manufacturing location (G = ETP, Texas, USA)

 

 

 

 

6−10

 

 

 

 

Sequential number

 

 

 

 

 

Fig. 4 — Serial Number Nomenclature

Unit Positioning — The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 5 for condensate connections for each unit position.

Typical positioning and alternate return air locations are shown in Fig. 5. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 6) for preferred suspension technique. The unit needs support underneath to prevent sagging.

IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.

LEGEND

Accessory Line

Alternate Air Intake and Discharge

Air Intake and Discharge

Note: Maintain recommended clearances per Figs. 2A–2B

Fig. 5 — Typical Unit Positioning

9

Image 9
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Unit Unit Weight Dimensions SizeDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units Unit 40RUS 40RUS Physical Data, English Chilled Water UnitsChilled Water Coil Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Fitting Requirements Factory-Installed Nozzle and Distributor DataUpper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 L Fitting RequirementTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Alternate Motors Electrical Data, Standard MotorsUnit Wiring Unit Voltage Maximum Holding Fan Contactor Coil DataManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishMotor Drive FAN DriveStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz SI Medium-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 Unit Airflow Pressure Drop FACTORY-SUPPLIED Pressure Drop EnglishPreliminary Information Comp A1 Comp B1 Check Voltage Imbalance