Carrier R-410A manual Check Voltage Imbalance, Comp A1 Comp B1

Page 36

CHECK VOLTAGE IMBALANCE

 

 

 

LINE-TO-LINE VOLTS:

AB ________ V

AC ______ V

BC

______ V

(AB + AC + BC)/3 = AVERAGE VOLTAGE = _______ V

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _______ V

 

 

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

__________ %

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START-UP

CHECK INDOOR FAN MOTOR SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

INTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

COMPRESSOR AMPS (L1/L2/L3)____/____/____ ____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING

OIL LEVEL AT 1/

to 1/ FULL?

(Y/N) ______

8

3

 

NOTES:

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231

Printed in Mexico

Edition Date: 09/09

 

Catalog No: 40RU-03SI

 

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Pg CL-2

Replaces: New

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Image 36
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Dimensions Size Unit Unit WeightDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units 40RUS Physical Data, English Chilled Water Units Unit 40RUSChilled Water Coil Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsFitting Requirement Upper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 LTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Wiring Fan Contactor Coil Data Unit Voltage Maximum HoldingLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishMotor Drive FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure DropPreliminary Information Check Voltage Imbalance Comp A1 Comp B1