Carrier R-410A manual FACTORY-SUPPLIED Pressure Drop English, Unit Airflow Pressure Drop

Page 34

Legend and Notes for Tables 10A and 10C

LEGEND

Bhp — Brake Horsepower Input to Fan

ESP — External Static Pressure

NOTES:

1.Maximum allowable fan speed for size 25 units is 1200 rpm . Maximum allowable fan speed for size 28 and 30 units is 1100 rpm.

2.Fan performance is based on deductions for wet coil, clean 2-in. filters, and unit casing. See table at right for factory-supplied filter pressure drop.

3.Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — ENGLISH

UNIT

AIRFLOW

PRESSURE DROP

(Cfm)

(in. wg)

 

40RUA*25

6,000

0.12

8,000

0.19

40RUS*25

10,000

0.26

 

40RUA*28

7,500

0.15

10,000

0.22

40RUS*28

12,500

0.30

 

40RUA*30

9,000

0.19

12,000

0.29

40RUS*30

15,000

0.40

 

Legend and Notes for Tables 10B and 10D

LEGEND

ESP — External Static Pressure

NOTES:

1.Maximum allowable fan speed for size 25 units is 20 r/s. Maximum allowable fan speed for size 28 and 30 units is 18.3 r/s.

2.Fan performance is based on deductions for wet coil, clean 51-mm filters, and unit casing. See table at right for factory-sup- plied filter pressure drop.

3.Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — SI

UNIT

AIRFLOW

PRESSURE DROP

(L/s)

(Pa)

 

40RUA*25

2900

32

3800

47

40RUS*25

4700

64

 

40RUA*28

3500

36

4700

55

40RUS*28

5900

76

 

40RUA*30

4250

47

5650

71

40RUS*30

7050

98

 

Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231

Printed in Mexico

Edition Date: 09/09

Catalog No: 40RU-03SI

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Replaces: New

34

Image 34
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Dimensions Size Unit Unit WeightDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units Chilled Water Coil 40RUS Physical Data, English Chilled Water UnitsUnit 40RUS Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsFitting Requirement Upper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 LTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Wiring Fan Contactor Coil Data Unit Voltage Maximum HoldingLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIMotor Drive Standard Drive Data, 60 Hz EnglishMedium-Static Drive Data, 60 Hz English FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure DropPreliminary Information Check Voltage Imbalance Comp A1 Comp B1