Carrier R-410A manual Fan Pulley Alignment Align as follows

Page 23

Fig. 23 — Fan Rotation

Fan Pulley Alignment — Align as follows:

1.Loosen setscrews on pulleys.

2.Align pulleys visually and tighten setscrews on fan pulley to lock it in place.

3.Use the methods shown in Fig. 24 to check proper pulley alignment.

4.If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until the pulleys are aligned.

5.Tighten motor holddown bolts.

Pulley and Drive Adjustment — To obtain desired fan speed, refer to the fan motor and drive data in Tables

8A-11D and adjust fan motor pulley as follows:

1.Remove belt from fan motor pulley after loosening motor from motor base.

2.Loosen setscrew in moveable flange of pulley. Screw moveable flange toward fixed flange to increase the fan speed and away from fixed flange to reduce speed. Before tightening setscrew, make certain that setscrew is over nearest flat surface of pulley hub (Fig. 24).

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment damage.

Increasing fan speed produces a greater load on motor. Do not exceed rated capacity of motor.

Condensate Drains — Keep condensate drains free of dirt and foreign matter.

Return-Air Filters — Refer to Replacing Filters section for filter accessibility and removal. Replace with clean filters of the sizes listed in Tables 1A-1D.

Chilled Water Coil Freeze Protection — Shut off water supply to unit. Remove side panel of unit and remove vent and drain plugs in top and bottom of coil header. Drain coil and blow out remaining water. Reinstall plugs and side panel.

Fig. 24 — Fan Pulley Adjustments

Alternative freeze protection methods follow:

Circulate hot water within the water coil’s supply main or supplementary space heating.

Close off supply lines to unit and open a union or field- supplied drain valve in the return line.

IMPORTANT: Draining from return line will not com- pletely drain water from coils.

After draining as much water as possible from coils, add sufficient antifreeze to prevent residual water in the coil from freezing.

Add a sufficient quantity of non-corrosive antifreeze to the entire system to prevent all water within the system from freezing.

Coil Removal — Remove unit panels and corner posts as required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit.

Cleaning Cooling Coil — Remove return-air filters. Remove any heavy dirt that may have accumulated on under- side of coil. Coil can be cleaned more easily with a stiff brush, vacuum cleaner, or compressed air when coil is dry. If coil is wet or if water is to be used for cleaning, guard against splash- ing water on electrical components or damaging surrounding area. Clean coil baffles as applicable and check for tight fit to be sure air does not bypass coil.

Cleaning Insulation — The insulation contains an im- mobilized antimicrobial agent that helps prevent the growth of bacteria and fungi. Clean the inner surface of the insulation according to the separate maintenance instructions shipped with the unit.

23

Image 23
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Unit Unit Weight Dimensions SizeDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units Steam Coil ‡ 40RUS Physical Data, English Chilled Water UnitsUnit 40RUS Chilled Water Coil40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Fitting Requirements Factory-Installed Nozzle and Distributor DataUpper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 L Fitting RequirementTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Alternate Motors Electrical Data, Standard MotorsUnit Wiring Unit Voltage Maximum Holding Fan Contactor Coil DataManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIFAN Drive Standard Drive Data, 60 Hz EnglishMedium-Static Drive Data, 60 Hz English Motor DriveStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz SI Medium-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 Unit Airflow Pressure Drop FACTORY-SUPPLIED Pressure Drop EnglishPreliminary Information Comp A1 Comp B1 Check Voltage Imbalance