Carrier R-410A manual Fan Contactor Coil Data, Unit Voltage Maximum Holding

Page 20

Table 6 — Fan Contactor Coil Data

UNIT

VOLTAGE

MAXIMUM

HOLDING

40RU**

(vac)

VA

 

 

25, 28, 30

24

10

Connecting Ductwork — Refer to the Carrier System Design Manual for the recommended design and layout of ductwork. Fig. 18 shows recommended duct connection to units with 2 fans.

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment damage.

Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pressure of zero in. wg. Failure to do so may result in motor overload.

DISCHARGE CONNECTIONS — Duct flanges are factory-supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field installation. Using the existing screws, install the duct flanges on the unit’s fan deck. Each fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. See Fig. 19. After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is important that this connection be properly fabricated to prevent high air friction losses and air noise.

RETURN CONNECTION — When using return-air ductwork, route return-air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit

removal for

servicing.

OUTDOOR-AIR INLET CONNECTION — Connect outdoor- air inlet to field-installed accessory economizer. Refer to Economizer Installation Instructions.

Return-Air Filters — Type and size of filters are shown in Tables 1A – 1D and are factory-supplied and factory- installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.

Fig. 18 — Typical Fan Discharge Connections for Multiple Fan Units

20

Image 20
Contents Installation, Start-Up Service Instructions PRE-INSTALLATION Dimensions Size Unit Unit WeightDimensions Sizes 28 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units 40RUS Physical Data, English Chilled Water Units Unit 40RUSChilled Water Coil Steam Coil ‡40RUS Physical Data, SI Chilled Water Units U a a 2 5 a 6 0 a 0 a Overhead Suspension Accessory Unit Size Unit Sizes 28 Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsFitting Requirement Upper 8 Long Radius Elbow 8 Nipple, 19 1/ 4 LTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Wiring Fan Contactor Coil Data Unit Voltage Maximum HoldingLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishMotor Drive FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIAirflow External Static Pressure kPa 577 1042 646 716 785 100 150 200 250 300 2830 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure DropPreliminary Information Check Voltage Imbalance Comp A1 Comp B1