Carrier 40RM007-034, 40RMQ008-028, 40RMS008-034 specifications Filter Removal/Replacement

Page 28

Replacing Filters — Filters can be removed and in- stalled from either side of the unit. Install new filters in units that have one fan as follows:

1. Remove the side access panel (retain screws).

2. Remove the filter retainer clip (see Fig. 25).

3. Remove old filters by lifting and tilting them out of the filter track. See Fig. 15 and 26.

4. Reverse the procedure to install new filters.

To install new filters in larger units that have 2 fans, follow the preceding steps, but use the factory-supplied filter hook to slide filters within reach for removal. The filter hook is shipped inside the unit in the filter track.

Do not operate unit without air filters.

Fig. 26 — Filter Removal/Replacement

FILTER

RETAINER

CLIP

Fig. 25 — Remove Filter Retainer Clip

28

Image 28
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units 40RMQ Physical Data, English Heat Pump Units Unit 40RMQ008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per Split40RMS Physical Data, English Chilled Water Units Unit 40RMS40RM Physical Data, SI Cooling Units Unit 40RM40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM014 40RM01640RM024 40RMQ01640RM028 40RM03440RMQ028 40RMS02840RM 016 - B 5 0 1 GC Unit007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Factory-Installed Nozzle and Distributor Data Fitting Requirements014-024 Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Cover Removed TypicalElectrical Data, Standard Motors MocpElectrical Data, Alternate Motors MocpEquip GNDHTR IFCLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor English40RMS 40RMQ Fan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIHigh-Static Drive Data, 60 Hz SI Medium-Static Drive Data, 60 Hz SI008 012 016 024 028 Standard Drive Data, 50 Hz English Medium-Static Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMSStandard Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz English014 034 008 012 016 024 Medium-Static Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SIUnit Airflow RMQExternal Static Pressure in. wg 40RM Cfm Rpm Bhp 800007 400 008 000External Static Pressure kPa 100 150 200 250 300850 990350 400 450 500 550 600 008 600 016 300921 975 1026 External Static Pressure kPa 100 150 200 250 300 008 1420016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Check Voltage Imbalance Comp A1 Comp B1