Carrier 40RMQ008-028, 40RM007-034, 40RMS008-034 specifications Fan Pulley Alignment Align as follows

Page 27

Fig. 23 — Fan Rotation

Fan Pulley Alignment — Align as follows:

1.Loosen setscrews on pulleys.

2.Align pulleys visually and tighten setscrews on fan pulley to lock it in place.

3.Use the methods shown in Fig. 24 to check proper pulley alignment.

4.If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until the pul- leys are aligned.

5.Tighten motor holddown bolts.

Pulley and Drive Adjustment — To obtain desired fan speed, refer to the fan motor and drive data in Tables 8A-

11D and adjust fan motor pulley as follows:

1.Remove belt from fan motor pulley after loosening motor from motor base.

2.Loosen setscrew in moveable flange of pulley. Screw moveable flange toward fixed flange to increase the fan speed and away from fixed flange to reduce speed. Be- fore tightening setscrew, make certain that setscrew is over nearest flat surface of pulley hub (Fig. 24).

Increasing fan speed produces a greater load on motor. Do not exceed rated capacity of motor.

Condensate Drains — Keep condensate drains free of dirt and foreign matter.

Return-Air Filters — Refer to Replacing Filters section for filter accessibility and removal. Replace with clean filters of the sizes listed in Tables 1A-1F.

Chilled Water Coil Freeze Protection — Shut off water supply to unit. Remove side panel of unit and remove vent and drain plugs in top and bottom of coil header. Drain coil and blow out remaining water. Reinstall plugs and side panel.

Fig. 24 — Fan Pulley Adjustments

Alternative freeze protection methods follow:

Circulate hot water within the water coil’s supply main or supplementary space heating.

Close off supply lines to unit and open a union or field- supplied drain valve in the return line.

IMPORTANT: Draining from return line will not com- pletely drain water from coils.

After draining as much water as possible from coils, add sufficient antifreeze to prevent residual water in the coil from freezing.

Add a sufficient quantity of non-corrosive antifreeze to the entire system to prevent all water within the system from freezing.

Coil Removal — Remove unit panels and corner posts as required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit.

Cleaning Cooling Coil — Remove return-air filters. Remove any heavy dirt that may have accumulated on under- side of coil. Coil can be cleaned more easily with a stiff brush, vacuum cleaner, or compressed air when coil is dry. If coil is wet or if water is to be used for cleaning, guard against splash- ing water on electrical components or damaging surrounding area. Clean coil baffles as applicable and check for tight fit to be sure air does not bypass coil.

Cleaning Insulation — The insulation contains an im- mobilized antimicrobial agent that helps prevent the growth of bacteria and fungi. Clean the inner surface of the insulation according to the separate maintenance instructions shipped with the unit.

27

Image 27
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units No. of Splits No. of Circuits per Split 40RMQ Physical Data, English Heat Pump UnitsUnit 40RMQ 008 012 016 024 028 Nominal Capacity TonsUnit 40RMS 40RMS Physical Data, English Chilled Water UnitsUnit 40RM 40RM Physical Data, SI Cooling Units40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RMQ016 40RM01440RM016 40RM02440RMS028 40RM02840RM034 40RMQ02840RMQ 40RMS 40RM 016 - B 5 0 1 GCUnit 007 008 010 012 014 016 024 028 034 40RMTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Fitting Requirements Factory-Installed Nozzle and Distributor Data014-024 Typical 40RMS Chilled Water Piping Condensate Drains Cover Removed Typical Wiring and Service Access Side Panel RemovedMocp Electrical Data, Standard MotorsMocp Electrical Data, Alternate MotorsIFC EquipGND HTRManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor English40RMS 40RMQ Fan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SI008 012 016 024 028 Unit 40RMQ 40RMS Standard Drive Data, 50 Hz EnglishMedium-Static Drive Data, 50 Hz English 40RMQ UnitHigh-Static Drive Data, 50 Hz English Standard Drive Data, 50 Hz SI014 034 008 012 016 024 High-Static Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SIRMQ Unit Airflow008 000 External Static Pressure in. wg 40RM CfmRpm Bhp 800 007 400990 External Static Pressure kPa100 150 200 250 300 850350 400 450 500 550 600 016 300 008 600921 975 1026 024 3300 External Static Pressure kPa 100 150 200 250 300008 1420 016 2830External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Comp A1 Comp B1 Check Voltage Imbalance