LEGEND

EQUIP

Equipment

GND

Ground

HC

Heating Contactor

HTR

Electric Heater

IFC

Indoor-Fan Contactor

IFM

Indoor-Fan Motor

TB

Terminal Block

T’STAT

Thermostat

 

Factory Wiring

 

Field Control Wiring

NOTE: Use copper conductors only.

Fig. 17 — Unit Wiring

Table 6 — Fan Contactor Coil Data

UNIT

VOLTAGE

MAXIMUM

40RM, 40RMQ

HOLDING

(vac)

40RMS

VA

 

007-034

24

10

Connecting Ductwork — Refer to the Carrier System Design Manual for the recommended design and layout of ductwork. Figure 18 shows recommended duct connection to units with 2 fans.

Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pres- sure of zero in. wg. Failure to do so may result in motor overload.

DISCHARGE CONNECTIONS — Duct flanges are factory-supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field installation. Us- ing the existing screws, install the duct flanges on the unit’s fan deck. Each fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. See Fig. 19. After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is im- portant that this connection be properly fabricated to prevent high air friction losses and air noise.

RETURN CONNECTION — When using return-air duct- work, route return-air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit removal for servicing.

OUTDOOR-AIR INLET CONNECTION — Connect outdoor- air inlet to field-installed accessory economizer. Refer to Economizer Installation Instructions.

Return-Air Filters — Type and size of filters are shown in Tables 1A-1F and are factory-supplied and factory-installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.

Fig. 18 — Typical Fan Discharge Connections

for Multiple Fan Units

24

Image 24
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units 40RMQ Physical Data, English Heat Pump Units Unit 40RMQ008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per Split40RMS Physical Data, English Chilled Water Units Unit 40RMS40RM Physical Data, SI Cooling Units Unit 40RM40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM014 40RM01640RM024 40RMQ01640RM028 40RM03440RMQ028 40RMS02840RM 016 - B 5 0 1 GC Unit007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Factory-Installed Nozzle and Distributor Data Fitting Requirements014-024 Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Cover Removed TypicalElectrical Data, Standard Motors MocpElectrical Data, Alternate Motors MocpEquip GNDHTR IFCLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor English40RMS 40RMQ Fan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SI008 012 016 024 028 Standard Drive Data, 50 Hz English Medium-Static Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMSHigh-Static Drive Data, 50 Hz English Standard Drive Data, 50 Hz SI014 034 008 012 016 024 Medium-Static Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SIUnit Airflow RMQExternal Static Pressure in. wg 40RM Cfm Rpm Bhp 800007 400 008 000External Static Pressure kPa 100 150 200 250 300850 990350 400 450 500 550 600 008 600 016 300921 975 1026 External Static Pressure kPa 100 150 200 250 300 008 1420016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Check Voltage Imbalance Comp A1 Comp B1