Carrier 40RMQ008-028 Cover Removed Typical, Wiring and Service Access Side Panel Removed

Page 21

Power Supply and Wiring — Check the unit data plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch of size required to provide adequate fan motor starting current. See Tables 4-6 for unit electrical data.

Install disconnect switch and power wiring in accordance with all applicable local codes. See Fig. 15-17 and the unit label diagram. For units with motor sizes less than 5 Hp (3.7 kW), connect power wiring to unit with no. 10 ring termi- nal. For units with motor sizes of 5 Hp (3.7 kW) or more, con- nect power wiring with 1/4-in. ring terminal.

The 40RM, 40RMQ and 40RMS size 007-016 units (except 40RM016 with YC or WD option) that have motors wired for

460-v, 3-ph, 60 Hz operation can be field-converted to 208/230-v, 3-ph, 60 Hz operation. Rewire the motor according to the diagram plate on the motor. After reconfiguring the mo- tor, mark the motor specifying 208-v or 230-v operation replac- ing the 460-v sticker information on the units’ corner post.

Fan motors are factory-installed on all units. Indoor-fan contactors are located in the fan contactor box behind the side access panel (see Fig. 15 and 16). Wire the thermostat to the 24-v control circuit terminal block located in the side of the fan contactor control box, according to Fig. 17 or the unit label diagram. If the air handler is part of a split system, complete the wiring from the condensing unit to the thermostat shown in Fig. 17.

FAN SCROLL

FAN

 

 

 

 

 

CONTACTOR

 

 

 

 

 

BOX

 

 

 

 

MOTOR

WIRE

 

 

 

 

AND DRIVE

 

 

 

 

 

ACCESS

 

 

 

 

 

 

 

 

A

 

 

 

 

 

J

 

 

 

 

 

R

 

 

 

 

 

V

 

 

FAN DRIVE

 

 

00

 

 

 

 

°5C

 

CONDENSATE

 

 

 

6

 

PULLEY

 

 

10

 

DRAIN

 

 

 

 

 

 

 

 

 

CONNECTION

 

 

 

 

 

(HORIZONTAL)

 

 

23

22

12

 

COIL

 

W

 

 

 

 

 

 

 

FILTER

TXV BULB

FAN

 

 

 

ELEMENTS

 

 

 

ACCESS

CONTACTOR

 

 

 

 

31

21

11

 

REFRIGERANT/

24V

 

 

 

 

CHILLED WATER

 

 

 

 

TERMINAL

 

 

 

 

PIPING ACCESS

 

 

 

FILTER

BLOCK

 

 

 

 

 

 

 

RETAINER

CONDENSATE

POWER

 

 

 

CLIP

 

 

 

 

DRAIN

WIRING

 

 

 

 

CONNNECTION

KNOCKOUT

 

 

 

 

(VERTICAL)

 

 

 

 

LEGEND

 

Fig. 16 — Fan Contactor Box and Terminal Block

TXV — Thermostatic Expansion Valve

 

 

(Cover Removed) (Typical)

Fig. 15 — Wiring and Service Access

(Side Panel Removed)

21

Image 21
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units Unit 40RMQ 40RMQ Physical Data, English Heat Pump Units008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per SplitUnit 40RMS 40RMS Physical Data, English Chilled Water UnitsUnit 40RM 40RM Physical Data, SI Cooling Units40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM016 40RM01440RM024 40RMQ01640RM034 40RM02840RMQ028 40RMS028Unit 40RM 016 - B 5 0 1 GC007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Fitting Requirements Factory-Installed Nozzle and Distributor Data014-024 Typical 40RMS Chilled Water Piping Condensate Drains Cover Removed Typical Wiring and Service Access Side Panel RemovedMocp Electrical Data, Standard MotorsMocp Electrical Data, Alternate MotorsGND EquipHTR IFCManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor English40RMS 40RMQ Fan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SI008 012 016 024 028 Medium-Static Drive Data, 50 Hz English Standard Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMSHigh-Static Drive Data, 50 Hz English Standard Drive Data, 50 Hz SI014 034 008 012 016 024 High-Static Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SIRMQ Unit AirflowRpm Bhp 800 External Static Pressure in. wg 40RM Cfm007 400 008 000100 150 200 250 300 External Static Pressure kPa850 990350 400 450 500 550 600 016 300 008 600921 975 1026 008 1420 External Static Pressure kPa 100 150 200 250 300016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Comp A1 Comp B1 Check Voltage Imbalance