Carrier 40RMS008-034 High-Static Drive Data, 60 Hz English, Standard Drive Data, 60 Hz SI

Page 32

Table 9C — High-Static Drive Data, 60 Hz — English

 

 

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

 

40RM

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

UNIT

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (in.)

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

4.3-5.3

Pulley Factory Setting

2.5

2.5

2.5

2.5

3.0

3.0

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (in.)

7.0

6.0*

6.0

6.0

7.4

7.9

7.4

8.6

8.6

Pulley Bore (in.)

1

1

1

1

17/16

17/16

17/16

115/16

115/16

Belt No. — Section

1—A

1—A

1—A

1—A

1—B

1—B

2—B

2—B

2—B

Belt Pitch (in.)

41.3

37.3

37.3

37.3

39.8

39.8

36.8

37.8

37.8

FAN SPEEDS (rpm)

 

 

 

 

 

 

 

 

 

Factory Setting

961

1121

1121

1121

979

1060

1118

1024

1024

Range

838-

978-

978-

978-

873-

950-

1014-

873-

873-

 

1084

1200*†

1200†

1200†

1096

1171

1200†

1075

1075

Max Allowable Speed (rpm)

1200

1200

1200

1200

1200

1200

1200

1100

1100

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

2

24.6

28.7

28.7

28.7

19.4

18.4

19.4

16.7

16.7

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

6

6

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (in.)

10.44-

10.44-

10.44-

10.44-

10.44-

9.16-

8.16-

6.67-

6.67-

 

12.32

12.32

12.32

12.32

12.32**

10.99

10.02

9.43

9.43

*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in. and result- ing fan speed is 837-1096 rpm.

†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

**575-v unit has a center distance of 9.16-10.99.

Table 9D — Standard Drive Data, 60 Hz — SI

 

40RM

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

UNIT

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

61.0-

71.1-

71.1-

86.4-

71.1-

71.1-

94.0-

109.2-

109.2-

 

86.4

96.5

96.5

111.8

96.5

96.5

119.4

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

224

224

224

224

229

229

239

279

279

Pulley Bore (mm)

25.4

25.4

25.4

25.4

36.5

36.5

36.5

49.2

49.2

Belt No. — Section

1—A

1—A

1—A

1—A

1—A

1—A

2—B

2—B*

2—B*

Belt Pitch (mm)

1024

1049

1049

1074

1074

1074

1062

(2) 1087

(2) 1087

 

(2) 1113

(2) 1113

 

 

 

 

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

Factory Setting

9.5

10.8

10.8

12.7

10.5

10.5

12.9

12.5

12.5

Range

7.8-11.1

9.2-12.4

9.2-12.4

11.1-14.4

9.0-12.1

9.0-12.1

11.3-14.4

11.4-14.0

11.2-13.9

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

20.0

20.0

18.3

18.3

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

2

0.327

0.327

0.327

0.328

0.318

0.318

0.255

0.218

0.218

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

5

5

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313

265-313

265-313

232-279

169-240

169-240

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

32

Image 32
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units 40RMQ Physical Data, English Heat Pump Units Unit 40RMQ008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per Split40RMS Physical Data, English Chilled Water Units Unit 40RMS40RM Physical Data, SI Cooling Units Unit 40RM40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM014 40RM01640RM024 40RMQ01640RM028 40RM03440RMQ028 40RMS02840RM 016 - B 5 0 1 GC Unit007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Factory-Installed Nozzle and Distributor Data Fitting Requirements014-024 Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Cover Removed TypicalElectrical Data, Standard Motors MocpElectrical Data, Alternate Motors MocpEquip GNDHTR IFCLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement 40RMS 40RMQ Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SI008 012 016 024 028 Medium-Static Drive Data, 60 Hz SIHigh-Static Drive Data, 60 Hz SI Standard Drive Data, 50 Hz English Medium-Static Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMS014 034 008 012 016 024 High-Static Drive Data, 50 Hz EnglishStandard Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SIUnit Airflow RMQExternal Static Pressure in. wg 40RM Cfm Rpm Bhp 800007 400 008 000External Static Pressure kPa 100 150 200 250 300850 990350 400 450 500 550 600 008 600 016 300921 975 1026 External Static Pressure kPa 100 150 200 250 300 008 1420016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Check Voltage Imbalance Comp A1 Comp B1