Carrier 40RMS008-034, 40RMQ008-028, 40RM007-034 Electrical Data, Alternate Motors, Mocp

Page 23

Table 5 — Electrical Data, Alternate Motors

UNIT

V*-PH-Hz

VOLTAGE

 

FAN MOTOR

 

POWER SUPPLY

LIMITS

Hp (kW)

 

FLA

Minimum

MOCP

 

 

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0/11.0

13.8/13.8

20

 

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5

9.4

15

40RM

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

007

 

575-3-60

518-632

2.0

(1.49)

 

2.4

3.0

15

 

 

230-3-50

207-253

2.4

(1.79)

 

5.2

6.5

15

 

 

400-3-50

360-440

2.4

(1.79)

 

2.6

3.3

15

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

15

40RM

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5/7.5

9.4/9.4

15

40RMQ

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

40RMS

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

008

 

 

 

 

 

 

 

 

 

 

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

 

 

 

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

20

 

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5

9.4

15

40RMS

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

010

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

 

 

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

40RM

 

208/230-3-60

187-253

3.7

(2.76)

 

10.5/10.5

13.3/13.3

20

 

460-3-60

414-506

3.7

(2.76)

 

4.8

6.0

15

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

40RMS

 

 

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

012

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

 

 

208/230-3-60

187-253

3.7

(2.76)

 

10.2

12.7

20

40RM

 

460-3-60

414-506

3.7

(2.76)

 

4.8

6.0

15

40RMS

 

575-3-60

518-632

5.0

(3.73)

 

5.1

6.4

15

014

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

 

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

40RM

 

208/230-3-60

187-253

5.0

(3.73)

 

14.6/12.8

18.3/16.0

30/25

 

460-3-60

414-506

5.0

(3.73)

 

6.4

8.0

15

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

5.0

(3.73)

 

5.1

6.4

15

40RMS

 

 

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

016

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

40RM

 

208/230-3-60

187-253

7.5

(5.59)

 

21.5/19.4

26.9/24.3

45/40

 

460-3-60

414-506

7.5

(5.59)

 

9.7

12.1

20

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

7.5

(5.59)

 

7.8

9.8

15

40RMS

 

 

 

230-3-50

207-253

7.5

(5.59)

 

22.8

28.5

50

024

 

 

 

 

400-3-50

360-440

7.5

(5.59)

 

11.4

14.3

25

40RM

 

208/230-3-60

187-253

10.0

(7.46)

 

28.2/26.8

35.3/33.5

60/60

 

460-3-60

414-506

10.0

(7.46)

 

13.4

16.8

30

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

10.0

(7.46)

 

10.3

12.9

20

40RMS

 

 

 

230-3-50

207-253

10.0

(7.46)

 

32.2

40.3

60

028

 

 

 

 

400-3-50

360-440

10.0

(7.46)

 

16.1

20.1

30

Legend and Notes For Tables 4 and 5

 

LEGEND

FLA

Full Load Amps

MOCP

Maximum Overcurrent Protection

*Motors are designed for satisfactory operation within 10% of nominal volt- ages shown. Voltages should not exceed the limits shown in the Voltage Lim- its column.

Determine maximum deviation from average voltage.

(AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v

Maximum deviation is 6 v.

Determine percent voltage imbalance.

NOTES:

1. Minimum circuit amps (MCA) and MOCP values are calculated in accor-

% Voltage Imbalance = 100 x

6

 

dance with NEC (National Electrical Code), Article 440.

2.

Motor FLA values are established in accordance with UL (Underwriters’

 

Laboratories) Standard 1995.

3.

Unbalanced 3-Phase Supply Voltage

 

Never operate a motor where a phase imbalance in supply voltage is

 

greater than 2%. Use the following formula to determine the percentage of

 

voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v

BC = 403 v

AC = 396 v

393 + 403 + 396

Average Voltage =

3

1192

=

3 = 397

397

= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

23

Image 23
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units No. of Splits No. of Circuits per Split 40RMQ Physical Data, English Heat Pump UnitsUnit 40RMQ 008 012 016 024 028 Nominal Capacity TonsUnit 40RMS 40RMS Physical Data, English Chilled Water UnitsUnit 40RM 40RM Physical Data, SI Cooling Units40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RMQ016 40RM01440RM016 40RM02440RMS028 40RM02840RM034 40RMQ02840RMQ 40RMS 40RM 016 - B 5 0 1 GCUnit 007 008 010 012 014 016 024 028 034 40RMTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Fitting Requirements Factory-Installed Nozzle and Distributor Data014-024 Typical 40RMS Chilled Water Piping Condensate Drains Cover Removed Typical Wiring and Service Access Side Panel RemovedMocp Electrical Data, Standard MotorsMocp Electrical Data, Alternate MotorsIFC EquipGND HTRManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement 40RMS 40RMQ Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor English Fan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz English008 012 016 024 028 Medium-Static Drive Data, 60 Hz SIHigh-Static Drive Data, 60 Hz SI Unit 40RMQ 40RMS Standard Drive Data, 50 Hz EnglishMedium-Static Drive Data, 50 Hz English 40RMQ Unit014 034 008 012 016 024 High-Static Drive Data, 50 Hz EnglishStandard Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SIRMQ Unit Airflow008 000 External Static Pressure in. wg 40RM CfmRpm Bhp 800 007 400990 External Static Pressure kPa100 150 200 250 300 850350 400 450 500 550 600 016 300 008 600921 975 1026 024 3300 External Static Pressure kPa 100 150 200 250 300008 1420 016 2830External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Comp A1 Comp B1 Check Voltage Imbalance