Carrier 40RMS008-034 High-Static Drive Data, 50 Hz English, Standard Drive Data, 50 Hz SI

Page 35

Table 10C — High-Static Drive Data, 50 Hz — English

 

 

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

 

40RM

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

UNIT

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (in.)

3.4-4.4

3.4-4.4

3.4-4.4

4.0-5.0

3.4-4.4

4.0-5.0

4.0-5.0

4.3-5.3

4.3-5.3

Pulley Factory Setting

2.5

2.5

2.5

3.0

2.5

3.0

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (in.)

6.0

5.5

5.5

5.5

6.0

7.0

6.4

8.0

8.6

Pulley Bore (in.)

1

1

1

1

17/

16

17/

16

17/

115/

16

115/

16

 

 

 

 

 

 

 

16

 

 

Belt No. — Section

1—A

1—A

1—A

1—A

2—A

2—A

2—A

2—B

2—B

Belt Pitch (in.)

37.3

37.3

37.3

36.3

36.3

39.3

34.3

36.8

37.8

FAN SPEEDS (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

926

1010

1010

1166

926

916

1002

855

795

Range

808-

881-

881-

1036-

808-

814-

891-

766-

713-

 

1045

1140

1140

1200*

1045

1018

1113

944

878

Max Allowable Speed (rpm)

1200

1200

1200

1200

1200

1200

1200

1100

1100

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

 

 

 

 

2

23.7

25.9

25.9

21.6

23.7

17.0

18.5

14.8

13.8

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

6

5

6

6

6

 

6

 

CLOSED POSITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (in.)

10.44-

10.44-

10.44-

9.16-

9.16-

9.16-

8.16-

6.67-

6.67-

 

12.32

12.32

12.32

10.99

10.99

10.99

10.02

9.43

9.43

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

Table 10D — Standard Drive Data, 50 Hz — SI

 

40RM

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

UNIT

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

61.0

71.1

71.1-

86.4-

86.4-

86.4-

109.2

109.2-

109.2-

 

86.4

96.5

96.5

111.8

111.8

111.8

134.6

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

203

203

203

203

229

229

218

279

279

Pulley Bore (mm)

25.4

25.4

25.4

25.4

36.5

36.5

36.5

49.2

49.2

Belt No. — Section

1—A

1—A

1—A

1—A

1—A

1—A

1—B

2—B

2—B

Belt Pitch (mm)

998

998

998

1024

1074

1074

1062

1113

1113

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

Factory Setting

8.6

9.8

9.8

11.6

10.3

10.3

13.3

10.4

10.4

Range

7.1-10.1

8.3-11.3

8.3-11.3

10.1-13.1

9.0-11.6

9.0-11.6

11.9-14.6

9.3-11.5

9.3-11.5

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

20.0

20.0

18.3

18.3

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

2

0.297

0.297

0.297

0.297

0.265

0.265

0.230

0.180

0.180

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

5

5

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313

265-313

265-313

232-279

169-240

169-240

35

Image 35
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units No. of Splits No. of Circuits per Split 40RMQ Physical Data, English Heat Pump UnitsUnit 40RMQ 008 012 016 024 028 Nominal Capacity TonsUnit 40RMS 40RMS Physical Data, English Chilled Water UnitsUnit 40RM 40RM Physical Data, SI Cooling Units40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RMQ016 40RM01440RM016 40RM02440RMS028 40RM02840RM034 40RMQ02840RMQ 40RMS 40RM 016 - B 5 0 1 GCUnit 007 008 010 012 014 016 024 028 034 40RMTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Fitting Requirements Factory-Installed Nozzle and Distributor Data014-024 Typical 40RMS Chilled Water Piping Condensate Drains Cover Removed Typical Wiring and Service Access Side Panel RemovedMocp Electrical Data, Standard MotorsMocp Electrical Data, Alternate MotorsIFC EquipGND HTRManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement 40RMS 40RMQ Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor English Fan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz English008 012 016 024 028 Medium-Static Drive Data, 60 Hz SIHigh-Static Drive Data, 60 Hz SI Unit 40RMQ 40RMS Standard Drive Data, 50 Hz EnglishMedium-Static Drive Data, 50 Hz English 40RMQ Unit014 034 008 012 016 024 High-Static Drive Data, 50 Hz EnglishStandard Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SIRMQ Unit Airflow008 000 External Static Pressure in. wg 40RM CfmRpm Bhp 800 007 400990 External Static Pressure kPa100 150 200 250 300 850350 400 450 500 550 600 016 300 008 600921 975 1026 024 3300 External Static Pressure kPa 100 150 200 250 300008 1420 016 2830External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Comp A1 Comp B1 Check Voltage Imbalance