Carrier 40RM007-034, 40RMQ008-028, 40RMS008-034 Lubricant Data, Manufacturer Lubricant

Page 25

Fig. 19 — Duct Flange Installation

START-UP

Before starting unit, check the following and correct as nec- essary:

Is unit solidly supported?

Is fan adjusted for speed and pulley alignment?

Are pulleys, motor, and bearings securely mounted?

Are there any loose parts that will rattle or vibrate?

Is condensate drain pan pitched for correct drainage?

Are coil baffle plates tight against coil to prevent air bypass?

Are all panels securely fastened?

Are all electrical connections correct and tight?

Also refer to condensing unit instructions before starting a split system. A split system start-up checklist is provided at the end of these instructions.

Fan Shaft Bearings — Bearings on size 007-012 units are sealed, permanently lubricated bearings that require no further lubrication. Size 014-034 units have pillow-block bear- ings (Fig. 20) that must be lubricated with suitable bearing grease approximately every 3 months. See Table 7 for suitable lubricants.

Table 7 — Lubricant Data

MANUFACTURER

LUBRICANT

Mobil

Mobilplex EP No. 2

Sunoco

Prestige 42

Texaco

Multifak 2

Texaco

Regal AFB-2*

*Preferred lubricant because it contains rust and oxidation inhibitors.

SERVICE

Inspection and maintenance should be performed at regular intervals and should include the following:

Complete cleaning of cabinet, fan wheel, cooling coil, condensate pan and drain, heating coils, and return-air grille (if present).

Inspection of panels and sealing of unit against air leakage.

Adjustment of fan motor, belt, bearings, and wheels.

Cleaning or replacement of filters.

Testing for cooling/heating system leaks.

Checking of all electrical connections.

Most unit service can be performed by removing one or both of the unit’s side panels. Coil cleaning or removal or insu- lation cleaning may require removal of a rear, top, or bottom panel, depending on the unit’s orientation. When service is completed, replace unit panels.

Panels — Panels are fastened to unit frame with sheet metal screws. Fan and coil compartment must be sealed tightly after service to prevent air from bypassing the cooling coil.

Fan Motor Lubrication — Fan motor supplied with unit is permanently lubricated and requires no further lubrication.

Fig. 20 — Fan Shaft, Bearings, and Fan Wheel

(Typical)

25

Image 25
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units Unit 40RMQ 40RMQ Physical Data, English Heat Pump Units008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per SplitUnit 40RMS 40RMS Physical Data, English Chilled Water UnitsUnit 40RM 40RM Physical Data, SI Cooling Units40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM016 40RM01440RM024 40RMQ01640RM034 40RM02840RMQ028 40RMS028Unit 40RM 016 - B 5 0 1 GC007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Fitting Requirements Factory-Installed Nozzle and Distributor Data014-024 Typical 40RMS Chilled Water Piping Condensate Drains Cover Removed Typical Wiring and Service Access Side Panel RemovedMocp Electrical Data, Standard MotorsMocp Electrical Data, Alternate MotorsGND EquipHTR IFCManufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement Fan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor English40RMS 40RMQ Fan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz SI Medium-Static Drive Data, 60 Hz SI008 012 016 024 028 Medium-Static Drive Data, 50 Hz English Standard Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMSStandard Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz English014 034 008 012 016 024 High-Static Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SIRMQ Unit AirflowRpm Bhp 800 External Static Pressure in. wg 40RM Cfm007 400 008 000100 150 200 250 300 External Static Pressure kPa850 990350 400 450 500 550 600 016 300 008 600921 975 1026 008 1420 External Static Pressure kPa 100 150 200 250 300016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Comp A1 Comp B1 Check Voltage Imbalance