Condensate Drain — Install a trapped condensate drain line to unit connection as shown in Fig. 13. The unit drain con- nection is a PVC stub. See Fig. 14. Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field-supplied threaded PVC adapter.

NOTE: A trap must be installed in the condensate drain line to ensure that the static pressure of fans is balanced with the water column in the drain line and that condensate can drain completely from pan. Without a trap, air can be drawn up drain line until water level in condensate pan becomes equal to static pressure created by fans, preventing complete drainage. Condi- tions will worsen as filters become dirty.

Install clean-out plugs in trap. Pitch drain line downward to an open floor drain or sump. Provide service clearance around drain line to permit removal of unit panels. Observe all local sanitary codes.

As shipped, the unit’s condensate drain pan is NOT sloped towards the drain connection. The pan slope must be changed to pitch towards the side of the unit with the drain connection.

OTE: Dimensions in [ ] are in millimeters.

Fig. 13 — Condensate Drains

See Fig. 14. Loosen the 2 screws next to the drain outlet at both ends of the unit, push drain pan down in the slots near the drain connection, and up in the slots on the opposite end. Retighten screws. The pan should have a pitch of at least 1/4-in. over its length toward the drain connection.

Fan Motors and Drives — Motor and drive packages are factory installed in all units. The standard motor and drive packages consist of the following items:

1 — fan motor

1 — adjustable motor pulley

1 — fan pulley

1 — fan belt (40RM007-012, 40RMQ008-012, 40RMS008-012 units)

2 — matched fan belts (40RM014-034, 40RMS014-034, 40RMQ014-028 units)

For instructions on changing fan rotation, changing drive speeds and adjusting drives, see Pulley and Drive Adjustment in the Service section.

Fig. 14 — Drain Pan Slope Adjustment

20

Image 20
Contents Installation, Start-Up Service Instructions Installation 40RM Physical Data, English Cooling Units 40RMQ Physical Data, English Heat Pump Units Unit 40RMQ008 012 016 024 028 Nominal Capacity Tons No. of Splits No. of Circuits per Split40RMS Physical Data, English Chilled Water Units Unit 40RMS40RM Physical Data, SI Cooling Units Unit 40RM40RMQ Physical Data, SI Heat Pump Units 40RMS Physical Data, SI Chilled Water Units Unit Unit Weight 40RM014 40RM01640RM024 40RMQ01640RM028 40RM03440RMQ028 40RMS02840RM 016 - B 5 0 1 GC Unit007 008 010 012 014 016 024 028 034 40RM 40RMQ 40RMSTypical Unit Positioning Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes TXV Sensing Bulb Location Factory-Installed Nozzle and Distributor Data Fitting Requirements014-024 Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Cover Removed TypicalElectrical Data, Standard Motors MocpElectrical Data, Alternate Motors MocpEquip GNDHTR IFCLubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Align as follows Filter Removal/Replacement 40RMS 40RMQ Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SI008 012 016 024 028 Medium-Static Drive Data, 60 Hz SIHigh-Static Drive Data, 60 Hz SI Standard Drive Data, 50 Hz English Medium-Static Drive Data, 50 Hz English40RMQ Unit Unit 40RMQ 40RMS014 034 008 012 016 024 High-Static Drive Data, 50 Hz EnglishStandard Drive Data, 50 Hz SI Medium-Static Drive Data, 50 Hz SI High-Static Drive Data, 50 Hz SIUnit Airflow RMQExternal Static Pressure in. wg 40RM Cfm Rpm Bhp 800007 400 008 000External Static Pressure kPa 100 150 200 250 300850 990350 400 450 500 550 600 008 600 016 300921 975 1026 External Static Pressure kPa 100 150 200 250 300 008 1420016 2830 024 3300External Static Pressure kPa 350 400 450 500 550 600 Unit Airflow Pressure Drop Copyright 2004 Carrier Corporation Preliminary Information Check Voltage Imbalance Comp A1 Comp B1