York YR manual Sound and Vibration Considerations, Brine Applications, Refrigerant Relief Piping

Page 21

FORM 160.81-EG1

nected in series and condenser water circuits connected in parallel. All of the chilled water flows through both cool- ers with each unit handling approximately one-half of the total load. When the load decreases to a customer se- lected load value, one of the units will be shut down by a sequence control. Since all water is flowing through the operating unit, that unit will cool the water to the de- sired temperature.

overflow valves or type tested Safety Pressure switches or a combination of these devices.

Sized to the requirements of applicable codes, a vent line must run from the relief device to the outside of the building. This refrigerant relief piping must include a cleanable, vertical-leg dirt trap to catch vent-stack con- densation. Vent piping must be arranged to avoid im- posing a strain on the relief connections and should include one flexible connection.

SOUND AND VIBRATION CONSIDERATIONS

A MAXE chiller is not a source of objectionable sound and vibration in normal air conditioning applications. Neo- prene isolation mounts are furnished as standard with each unit. Optional level-adjusting spring isolator assem- blies designed for 1" static deflection are available.

FIG. 2 – SERIES EVAPORATORS PARALLEL CONDENSERS

BRINE APPLICATIONS

LD00508

MAXE chiller sound pressure level ratings will be fur- nished upon request.

Control of sound and vibration transmission must be taken into account in the equipment room construction as well as in the selection and installation of the equipment.

The YR Screw Chiller, utilizing the Frick Refrigeration com- pressor, is a good match for the high head requirements of low temperature brine applications. This is particularly true of thermal ice storage systems, typically requiring 22°F (–5.6°C) to 24°F (–4.4°C) leaving brine temperatures. This performance is enhanced with the standard thermal stor- age control mode described on page 6.

Particular attention must be paid to the application of two or more chillers with evaporators in parallel or se- ries when the brine temperature is below 32°F (0°C). The brine MUST NOT flow through the evaporator of the idle chiller, because it can cause the condenser wa- ter to freeze. A bypass or other type of arrangement is required that shuts off flow to the idle evaporator. When units are applied in series with lead/lag capability, the units should be identical.

REFRIGERANT RELIEF PIPING

Each chiller is equipped with pressure relief devices. The purpose of the relief devices is to quickly relieve excess pressure of the refrigerant charge to atmosphere, as a safety precaution in the event of an emergency such as a fire. They are set to relieve at an internal pressure of 235 psig (1620 kPa) and are located on the condenser, evaporator and oil separator; and are pro- vided in accordance with ASHRAE 15 Safety Code and ASME or applicable pressure vessel code. Under these circumstances the relief devices may be relief valves,

THERMAL INSULATION

No appreciable operating economy can be achieved by thermally insulating the chiller. However, the chiller’s cold surfaces should be insulated with a vapor barrier insulation sufficient to prevent condensation. A chiller can be factory insulated with 3/4" (19mm) or 1-1/2" (38mm) thick insulation, as an option. This insulation will normally prevent condensation in environments with dry bulb temperatures of 50°F to 90°F (10°C to 32°C) and relative humidities up to 75% [3/4" (19mm) thickness] or 90% [1-1/2" (38mm) thickness]. The in- sulation is painted and the surface is flexible and rea- sonably resistant to wear. It is intended for a chiller installed indoors and, therefore, no protective cover- ing of the insulation is usually required. If insulation is applied to the water boxes at the job site, it must be removable to permit access to the tubes for routine maintenance.

VENTILATION

The ASHRAE Standard 15 Safety Code for Mechani- cal Refrigeration requires that all machinery rooms be vented to the outdoors utilizing mechanical ventilation by one or more power-driven fans. This standard, plus National Fire Protection Association Standard 90A, state, local and other related codes should be reviewed for specific requirements.

YORK INTERNATIONAL

21

Image 21
Contents Ashrae 90.1Compliant Table of Contents Introduction ARI Certification Program RatingsComputerized Performance Ratings OFF-DESIGN PerformanceOptiview Control Center OptiView Control CenterDisplay Only Programmable On Setpoint Off Setpoint Set Date Set Time Clock Enabled/Disabled 12/24 Hour Time Remaining Until Next Print Display Messages Solid State Starter Only Lcsss Mechanical Specifications Refrigerant System Mechanical Specifications Form 160.81-EG1General Control PanelYork International Codes and Standards Startup and Operator TrainingIsolation Mounting Refrigerant ContainmentAccessories and Modifications Marine Water Boxes SI Metric Conversion KNOCK-DOWN Shipment Refrigerant STORAGE/RECYCLING SystemApplication Data LocationWater Circuits Parallel Evaporators Parallel Condensers Multiple UnitsBrine Applications Sound and Vibration ConsiderationsRefrigerant Relief Piping Thermal InsulationElectrical Considerations Ampacity on Line Side of StarterMotor Electrical Data FLA = 50 HZ Electrical Data Motor END Compressor TOP View DimensionsWater BOX Dimensions FT. DIM Evaporators T Condenser T Pass Evaporators Compact Water Boxes Dimensions Ft.-In. Nozzle ArrangementsEvaporators Compact Water Boxes Dimensions mm Nozzle ArrangementsCondensers Compact Water Boxes Passes Neoprene Isolators Dimensions In. Floor LayoutDimensions mm Floor Layout Spring Isolators Dimensions Floor LayoutWeights Unit WeightsSolid State Starter Weight Guide Specifications CompressorLubrication System Evaporator MotorCondenser Refrigerant SystemOptiview Control Center Compressor Motor Starter OPTION, 200 START-UP and Operator Training Portable Refrigerant STORAGE/RECY- Cling System