FORM
n.Oil - high pressure
o.Control panel - power failure
p.Watchdog - software reboot
5.1.Safety shutdowns with a Solid State Starter (LCSSS) shall include:
a.Shutdown - requesting fault data...
b.High instantaneous current
c.High phase (X) heatsink temperature - running
d.105% motor current overload
e.Motor or starter - current imbalance
f.Phase (X) shorted SCR
g.Open SCR
h.Phase rotation
6.Cycling shutdowns enunciated through the display and the status bar, and consisting of system sta- tus, system details, day, time, cause of shutdown, and type of restart required.
Cycling shutdowns shall include:
a.Multiunit cycling - contacts open
b.System cycling - contacts open
c.Control panel - power failure
d.Leaving chilled liquid - low temperature
e.Leaving chilled liquid - flow switch open
f.Condenser - flow switch open
g.Motor controller - contacts open
h.Motor controller - loss of current
i.Power fault
j.Control panel - schedule
6.1Cycling shutdowns with a Solid State Starter (LCSSS) shall include:
a.Initialization failed
b.Serial communications
c.Requesting fault data
d.Stop contacts open
e.Power fault
f.Low phase (X) temperature sensor
g.Run signal
h.Invalid current scale selection
i.Phase locked loop
j.Low supply line voltage
k.High supply line voltage
l.Logic board processor
m.Logic board power supply n. Phase loss
7.Security access to prevent unauthorized change of setpoints, to allow local or remote control of the chiller, and to allow manual operation of the variable orifice and slide valve position. Access shall be through ID and password recognition, which is defined by three different levels of user competence: view, operator, and service.
8.Trending data with the ability to customize points of once every second to once every hour. The panel shall trend up to 6 different parameters from a list of over 140, without the need of an external moni- toring system.
9.The operating program stored in
10.A fused connection through a transformer in the compressor motor starter to provide individual
11.A numbered terminal strip for all required field in- terlock wiring.
12.An
13.The capability to interface with a building automa- tion system to provide:
a.Remote chiller start and stop
b.Remote leaving chiller liquid temperature adjust
c.Remote current limit setpoint adjust
d.Remote ready to start contacts
e.Safety shutdown contacts
f.Cycling shutdown contacts
g.Run contacts
COMPRESSOR MOTOR STARTER (OPTION, 200 - 600V)
The chiller manufacturer shall furnish a
YORK INTERNATIONAL | 39 |