The SETPOINTS screen provides a convenient loca- tion for programming the most common setpoints in- volved in the chiller control. The Setpoints are shown on other individual screens, but to cut down on need- less searching, they can all be found on this screen. This screen also serves as a gateway to a
Display Only:
•Leaving Chilled Liquid Temperature – Setpoint
•Leaving Chilled Liquid Temperature Cycling – Shutdown
•Leaving Chilled Liquid Temperature Cycling – Restart
•Current Limit Setpoint
Programmable:
•Local Leaving Chilled Liquid Temperature – Range
•Local Leaving Chilled Liquid Temperature – Setpoint
•Leaving Chilled Liquid Temperature Cycling Offset – Shutdown
•Leaving Chilled Liquid Temperature Cycling Offset – Restart
•Remote Analog Input Range
•Local Motor Current Limit
•Pulldown Demand Limit
•Pulldown Demand Time
The SETUP is the top level of the general configura- tion parameters. It allows programming of the time and date, along with specifications as to how the time will be displayed. In addition, the chiller configuration as determined by the Micro Board program jumpers and program switches is displayed. From this screen you can perform the following:
Display Only:
•Chilled Liquid Pump Operation (Displays Standard or Enhanced)
•
•Power Failure Restart (Displays Manual or Automatic)
•Liquid Type (Displays Water or Brine)
Programmable:
•Set Date
•Set Time
•Clock (Enabled/Disabled)
•12/24 Hour
The following six subscreens can be accessed from the SETUP screen:
The SCHEDULE screen contains more programmable values than a normal display screen. Each program- mable value is not linked to a specific button; instead, the select key is used to enable the cursor arrows and check key to program the Start/Stop times for any day of the week up to 6 weeks in advance. The user has the ability to define a standard set of Start/Stop times that are utilized every week or specify exceptions to create a special week.
Programmable:
•Exception Start/Stop Times
•Schedule (Enable/Disable)
•Repeat Sunday Schedule
•Standard Week Start/Stop Times
•Reset All Exception Days
•Select