York YR manual On Setpoint Off Setpoint

Page 8

OptiView Control Center (continued)

FORM 160.81-EG1

Slide Valve Unload (Manual)

Slide Valve Auto

Max. Load Temperature

Minimum Load FLA

Minimum Load Control Source

The HOT GAS BYPASS screen, accessed from the COMPRESSOR screen, displays a pictorial of the by- pass line and solenoid valve location on the chiller. The Hot Gas ON and OFF Setpoints are programmed on this screen and system parameters pertinent to Hot Gas Bypass operation are displayed. An LED illuminates when the Hot Gas solenoid is ON. If the chiller is equipped with the Hot Gas Bypass option, operation must be enabled on the OPERATIONS screen. From this screen you can perform the following:

Display Only:

Slide Valve Position

Return Chilled Liquid Temperature

Leaving Chilled Liquid Temperature

Hot Gas Solenoid (LED)

Programmable:

On Setpoint

Off Setpoint

The SLIDE VALVE CALIBRATION screen displays a cutaway view of the chiller compressor, revealing the rotary screw and slide valve and provides the capabil- ity of calibrating the slide valve. From this screen, you can perform the following:

Display Only:

Slide Valve Loading (LED)

Slide Valve Unloading (LED)

Calibration Message

Programmable:

Start Calibration

Cancel Calibration

The OIL SEPARATOR screen displays a close-up view of the chiller oil separator/sump.

Display Only:

Discharge Temperature

Discharge Superheat

Oil Pressure

Discharge Pressure

Differential Oil Pressure

Differential Filter Pressure

Oil Return Solenoid (LED)

Evaporator Pressure

Condenser Pressure

Condenser Saturation

1.The MOTOR “soft” key on the HOME screen, when pressed, shows a picture of either a YORK Electro- Mechanical Starter or a Solid State Starter, depend- ing on chiller configuration. The Programmable pulldown demand to automatically limit motor load- ing can be used to minimize building demand charges. Pulldown time period control over four hours, and verification of time remaining in pulldown cycle from display readout. Separate digital setpoint for current limiting between 30 and 100%.

The ELECTRO-MECHANICAL STARTER (E–M) screen displays a picture of the starter and the follow- ing values. The ones below are common among both offerings and the values will be displayed on both types of starter screens. From this screen you can perform the following:

Display Only:

Motor Run (LED)

Motor Current % Full-load Amps

Current Limit Setpoints

Pulldown Demand Time Left

Programmable:

Local Motor Current Limit

Pulldown Demand Limit

Pulldown Demand Time

The SOLID STATE STARTER (SSS) screen displays a picture of the starter and the following values, which are displayed in addition to the common ones listed above. From this screen, you can perform the following:

Display Only:

Input Power kW

kW Hours

Starter Model

Voltage – Phase A, B, C

Current – Phase A, B, C

Temperature – Phase A, B, C

8

YORK INTERNATIONAL

 

Image 8
Contents Compliant Ashrae90.1 Table of Contents Introduction Ratings ARI Certification ProgramComputerized Performance Ratings OFF-DESIGN PerformanceOptiView Control Center Optiview Control CenterDisplay Only Programmable On Setpoint Off Setpoint Set Date Set Time Clock Enabled/Disabled 12/24 Hour Time Remaining Until Next Print Display Messages Solid State Starter Only Lcsss Mechanical Specifications Mechanical Specifications Form 160.81-EG1 Refrigerant SystemGeneral Control PanelYork International Startup and Operator Training Codes and StandardsIsolation Mounting Refrigerant ContainmentAccessories and Modifications SI Metric Conversion Marine Water BoxesKNOCK-DOWN Shipment Refrigerant STORAGE/RECYCLING SystemWater Circuits Application DataLocation Multiple Units Parallel Evaporators Parallel CondensersSound and Vibration Considerations Brine ApplicationsRefrigerant Relief Piping Thermal InsulationMotor Electrical Data Electrical ConsiderationsAmpacity on Line Side of Starter FLA = 50 HZ Electrical Data Motor END Compressor Dimensions TOP ViewWater BOX Dimensions FT. DIM Evaporators T Condenser T Pass Dimensions Ft.-In. Nozzle Arrangements Evaporators Compact Water BoxesDimensions mm Nozzle Arrangements Evaporators Compact Water BoxesCondensers Compact Water Boxes Passes Dimensions In. Floor Layout Neoprene IsolatorsDimensions mm Floor Layout Dimensions Floor Layout Spring IsolatorsSolid State Starter Weight WeightsUnit Weights Lubrication System Guide SpecificationsCompressor Motor EvaporatorCondenser Refrigerant SystemOptiview Control Center Compressor Motor Starter OPTION, 200 Portable Refrigerant STORAGE/RECY- Cling System START-UP and Operator Training