Application Data

The following is a user’s guide in the application and installation of MAXE Chillers, and will ensure the reli- ability and trouble-free life for which this equipment was designed. While this guide is directed towards normal, water-chilling applications, the YORK sales represen- tatives can provide complete recommendations on other types of applications.

Location

MAXE Chillers are virtually vibration-free and generally can be located at any level in a building where the con- struction will support the total system operating weight.

The unit site must be a floor, mounting pad or founda- tion which is level within 1/4" (6.4 mm) and capable of supporting the operating weight of the chiller.

Sufficient clearance to permit normal service and main- tenance work should be provided all around and above the unit. Additional space should be provided at one end of the unit to permit cleaning of evaporator and condenser tubes as required. A doorway or other prop- erly located opening may be used.

The chiller should be installed in an indoor location where temperatures range from 40°F to 110°F (4.4°C to 43.3°C).

Water Circuits

Flow Rate – For normal water chilling duty, evaporator flow rates are permitted at water velocity levels in the heat exchangers tubes of between 3 ft./second and 12 ft./sec- ond (0.91 m/s and 3.66 m/s). Condenser flow rates are permitted between 3.33 ft./sec. and 12 ft./sec. (1.01 m/s and 3.66 m/s). Variable flow applications are possible, and initial chiller selections should be made accordingly to permit proper range of flow while maintaining the mini-

mum velocity noted above. Variable flow in the condenser is not recommended, as it generally raises the energy con- sumption of the system by keeping the condenser pres- sure high in the chiller. Additionally, the rate of fouling in the condenser will increase at lower water velocities asso- ciated with variable flow, raising system maintenance costs. Cooling towers typically have narrow ranges of operation with respect to flow rates, and will be more effective with full design flow. Ref. Table 1 for flow limits.

Temperature Ranges – For normal water chilling duty, leaving chilled water temperatures may be selected be- tween 38°F (3.3°C) [36°F (2.2°C) with Smart Freeze en- abled) and 70°F (21.1°C) for water temperature ranges between 3°F and 30°F (1.7°C and 16.7°C).

Water Quality – The practical and economical application of liquid chillers requires that the quality of the water supply for the condenser and evaporator be analyzed by a water treatment specialist. Water quality may affect the perfor- mance of any chiller through corrosion, deposition of heat- resistant scale, or sedimentation or organic growth. These will degrade chiller performance and increase operating and maintenance costs. Normally, performance may be main- tained by corrective water treatment and periodic cleaning of tubes. If water conditions exist which cannot be corrected by proper water treatment, it may be necessary to provide a larger allowance for fouling, and/or to specify special mate- rials of construction.

General Piping – All chilled water and condenser water piping should be designed and installed in accordance with accepted piping practice. Chilled water and condenser water pumps should be located to discharge through the chiller to assure positive pressure and flow through the unit. Piping should include offsets to provide flexibility and should be arranged to prevent drainage of water from the

TABLE 1 – WATER FLOW RATE LIMITS – GPM (L/s)

 

SHELL

PASS

 

EVAPORATOR

 

 

CONDENSER

 

 

 

CODE

MINIMUM

 

MAXIMUM

MINIMUM

 

MAXIMUM

 

 

 

 

 

 

 

 

TB, VB

1

383

(24.2)

 

1525

(96.2)

613

(38.7)

 

2204

(139.1)

 

 

2

192

(12.1)

 

762

(48.1)

307

(19.4)

 

1102

(69.5)

 

 

 

3

128

(8.1)

 

508

(32.1)

205

(12.9)

 

734

(46.3)

 

 

TC, VC

1

468

(29.5)

 

1866

(118.0)

683

(43.1)

 

2455

(154.9)

 

 

2

234

(14.8)

 

932

(58.8)

342

(21.6)

 

1227

(77.4)

 

 

 

3

157

(9.9)

 

621

(39.2)

228

(14.4)

 

818

(51.6)

 

 

 

1

570

(36.0)

 

2277

(143.7)

771

(48.7)

 

2774

(175.0)

 

 

TD, VD

2

286

(18.0)

 

1138

(71.8)

386

(24.4)

 

1386

(87.5)

 

 

 

3

–––

–––

 

–––

–––

–––

–––

 

–––

–––

 

WB, XB

1

693

(43.7)

 

2771

(174.9)

866

(54.6)

 

3462

(218.5)

 

 

2

346

(21.8)

 

1385

(87.4)

433

(27.3)

 

1731

(109.2)

 

 

 

3

231

(14.6)

 

924

(58.3)

289

(18.2)

 

1154

(72.8)

 

 

WC, XC

1

822

(51.9)

 

3287

(207.4)

1082

(68.3)

 

4328

(273.1)

 

 

2

411

(25.9)

 

1644

(103.7)

541

(34.1)

 

2164

(136.5)

 

 

 

3

274

(17.3)

 

1096

(69.2)

361

(22.8)

 

1443

(91.1)

 

 

WD, XD

1

986

(62.2)

 

3945

(248.9)

1350

(85.2)

 

5400

(340.1)

 

 

2

493

(31.1)

 

1972

(124.4)

675

(42.6)

 

2700

(170.0)

 

 

 

3

–––

–––

 

–––

–––

–––

–––

 

–––

–––

YORK INTERNATIONAL

19

Image 19
Contents 90.1 AshraeCompliant Table of Contents Introduction OFF-DESIGN Performance RatingsARI Certification Program Computerized Performance RatingsOptiview Control Center OptiView Control CenterDisplay Only Programmable On Setpoint Off Setpoint Set Date Set Time Clock Enabled/Disabled 12/24 Hour Time Remaining Until Next Print Display Messages Solid State Starter Only Lcsss Mechanical Specifications Control Panel Mechanical Specifications Form 160.81-EG1Refrigerant System GeneralYork International Refrigerant Containment Startup and Operator TrainingCodes and Standards Isolation MountingAccessories and Modifications Refrigerant STORAGE/RECYCLING System SI Metric ConversionMarine Water Boxes KNOCK-DOWN ShipmentLocation Application DataWater Circuits Parallel Evaporators Parallel Condensers Multiple UnitsThermal Insulation Sound and Vibration ConsiderationsBrine Applications Refrigerant Relief PipingAmpacity on Line Side of Starter Electrical ConsiderationsMotor Electrical Data FLA = 50 HZ Electrical Data Motor END Compressor TOP View DimensionsWater BOX Dimensions FT. DIM Evaporators T Condenser T Pass Evaporators Compact Water Boxes Dimensions Ft.-In. Nozzle ArrangementsEvaporators Compact Water Boxes Dimensions mm Nozzle ArrangementsCondensers Compact Water Boxes Passes Neoprene Isolators Dimensions In. Floor LayoutDimensions mm Floor Layout Spring Isolators Dimensions Floor LayoutUnit Weights WeightsSolid State Starter Weight Compressor Guide SpecificationsLubrication System Refrigerant System MotorEvaporator CondenserOptiview Control Center Compressor Motor Starter OPTION, 200 START-UP and Operator Training Portable Refrigerant STORAGE/RECY- Cling System