OptiView Control Center (continued)
FORM
tacts include a Remote Mode Ready To Start, a Cy- cling Shutdown, a Safety Shutdown and a chiller Run Contact. Pressure transducers sense system pressures and thermistors sense system temperatures. The out- put of each transducer is a DC voltage that is analo- gous to the pressure input. The output of each ther- mistor is a DC voltage that is analogous to the tem- perature it is sensing.
Setpoints can be changed from a remote location via
This printed circuit board requests the required data from the Micro Board and makes it available for the YORK ISN network. This optional board is available through the YORK BAS group. The operating program is stored in
Smart Freeze Point Protection can operate the chiller as low as 36°F (2.22°C) leaving chilled water tempera- ture, without nuisance trips on Low Water Temperature. The sophisticated program and sensor monitors the chiller water temperature to prevent
Thermal ice storage systems are based on the concept of using
When power is applied to the chiller, the HOME screen is displayed. This screen displays a visual representation of the chiller and a collection of data detailing important op- erations and parameters. When the chiller is running, the flow of chilled liquid is animated by the alternating shades of color moving in and out of the pipe nozzles. The pri- mary values that need to be monitored and controlled are shown on this screen. They are as follows:
Display Only:
•Chilled Liquid Temperature – Leaving
•Chilled Liquid Temperature – Return
•Condenser Liquid Temperature – Return
•Condenser Liquid Temperature – Leaving
•Motor Run (LED)
•%
•Operating Hours
With the “soft” keys the operator is only one touch away from the 8 main screens that allow access to the major information and components of the chiller. The 8 screens are the SYSTEM, EVAPORATOR, CONDENSER, COM- PRESSOR, OIL SUMP, MOTOR, SETPOINTS, and the HISTORY. Also on the Home Screen is the ability to Log IN, Log OUT and Print. Log In and Log Out is the means by which different security levels are accessed.
The SYSTEM screen gives a general overview of com- mon chiller parameters for both shells. This is an end view of the chiller with a
Display Only:
•Discharge Temperature
•Chilled Liquid Temperature – Leaving
•Chilled Liquid Temperature – Return
•Chilled Liquid Temperature – Setpoint
•Evaporator Pressure
•Evaporator Saturation Temperature
•Condenser Liquid Temperature – Leaving
•Condenser Liquid Temperature – Return
•Condenser Pressure
•Condenser Saturation Temperature
•Oil Temperature
•Differential Oil Pressure
•%
•Current Limit
•Slide Valve Position
6 | YORK INTERNATIONAL |
|