STARTING/
STOPPING THE
CHILLER
If you disconnect the Chiller from the main power supply and reconnect it, the Chiller needs 15 minutes for the crankcase heater to warm up. You can not use the Chiller during this time.
Plug in the power cord to restore power after any required maintenance.
The chiller control automatically performs its bootup routine. When bootup is complete, the screen displays the To Process temperature. The chiller is ready to run.
Press the Start Chiller button.
Check the Pump and Compressor lights on the control panel; they should turn on and off as the pump and com- pressor cycle on and off. The To Process temperature dis- plays on the control. The To Process temperature is real- time temperature. It should change as the chiller runs and cools the fluid.
To safely stop the chiller at any time, press the red Stop Chiller button on the control panel.
The chiller remains on, but stopped. The display screen on the control remains on.
NOTE: When you press the Stop Chiller button, the pump and compressor both stop. If you want to restart immediately by pressing the Start Chiller button, the pump will turn on but the compressor will not turn on for three minutes. The Process Pump light on the control panel will light immediately. After three minutes the compressor turns on and the Compressor light on the control panel lights.