4 Check the continuity within the switch
and make sure it corresponds to the following conditions:
Item | Description |
|
|
High Pressure Switches | Cut out @ 300 PSIG on rise |
Low Pressure Switches | Cut out at 28 PSIG on fall |
| Cut in at 43 PSIG on rise |
|
|
If required, check the switch with a refrigeration gauge. If the switch does not change, as listed in this table, when compared to a refrigeration pressure gauge, the switch is faulty. Replace the switch.