Use this table when configuring the temperature controller. Refer to the manufacturer’s manual that accompanies this User Guide for detailed information.
When the control displays the text listed in the Display col- umn, you can scroll to, and change, the settings listed in the Parameter column.
CONTROL SETTINGS
Display | Parameter | Description | Setting | Units |
InP | SP.LL | Lower Setpoint limit | 40 | °F |
| SP.HL | Upper Setpoint Limit | 70 | °F |
| TyPE | Input sensor type | rtd | 100 ohm rtd |
DSPL | dspl | Display menu | ||
| Unit | Temperature units | F | °F or °C |
|
|
|
|
|
OutP | O1.ty | Output 1 Type | PID | |
| O1.ac | Output 1 action | re | Reverse action |
| O1.cy | Output 1 cycle type | 5 | Seconds |
| O1.hl | Output 1 High limit | 80% | % time HGV is on |
| O2.ty | Output 2 Control Type | ALr | |
| O2.aa | Output 2 Alarm 1 Action | nor | |
| O2.ao | Output 2 process | DE.L | Alarm set to low deviation |
| O2.ih | Output 2 alarm inhibit | En | Enabled |
| O2.SP | Output 2 alarm setpoint | 4 | °F Low deviation |
Cnrl | Pb1 | Proportional | 1 | |
| der | Derivative Action - rate | 0 | |
| OFFS | Manual reset | OFF | |
| Int | Integral Action - reset | 0 | |
|
|
|
|
|
UGH016/0601 | Series 1 Portable Chillers, TIC Control | APPENDIX |