
The Conair Portable Chiller uses a standard 100 ohm RTD to monitor process temperature. Disconnect the RTD leads and measure the resistance through the RTD. It should read 95 - 110 ohms. If it does not, the RTD is bad and needs replaced.
To replace the RTD:
1 Disconnect and lockout power to the chiller.
2 Disconnect the To Process tubing from the
To Process connection.
Fill/Drain valve
To Process connection
CHECKING AND REPLACING THE
RTD
3 Open the Drain/Fill valve and drain water
from the unit so the water level is lower that the RTD.
4 Open the side of the chiller.
5 Disconnect the RTD wiring from the
temperature controller in the top electrical panel. Refer to the wiring diagram.
6 Remove the RTD.
Loosen the compression nut to slide the RTD out of the evaporator.
7 Install the new RTD.
The new RTD should be inserted in the evaporator so that the tip is extended completely through the evaporator.
8 Wire the RTD to the controller
in the top electrical enclosure.
Always refer th the wiring diagrams that came with your chiller to locate specific electrical components.
RTD
UGH016/0500 | Series 1 Portable Chillers, TIC Control TROUBLESHOOTING |