MECHANICAL
CONDITIONS
CONT’D
Alarm | Possible cause | Solution |
|
|
|
High Discharge Pressure (pump is running, compressor is off)
Clogged/dirty | Clean the coil. See Cleaning |
condenser. | the |
| the Maintenance section. |
Blocked air flow to air- | Move chiller or unblock air |
cooled condenser. | passageway. |
|
|
Low condenser water | Check required flow; see |
flow or water too warm | Specifications in the |
to | Description section. |
denser. |
|
Blocked condenser water Unblock line; open valve. line or valve closed.
Clean the condenser. See Cleaning the
UGH016/0500 | Series 1 Portable Chillers, TIC Control TROUBLESHOOTING |