MECHANICAL
CONDITIONS
CONT’D
Alarm | Possible cause | Solution |
Low Suction Pressure (pump is running and com- pressor is off)
No or low flow with a | ❏ Check To Process and From |
failed flow switch and | Process valves to see if they |
RTD. | are open. |
| ❏ Check Flow switch and |
| RTD. Replace as needed. |
|
|
Compressor suction valve | Open valve. |
is closed. |
|
|
|
No load on the Chiller. | Check process load for |
| required load. Chiller may be |
| oversized. |
|
|
The Evaporator is fouled. | Clean Evaporator. See |
| Cleaning the Evaporator or |
| |
| Maintenance section. |
|
|
The Evaporator is frozen. | ❏ Check RTD; Replace as |
| needed. |
| ❏ Check minimum allowable |
| setpoint for percent glycol |
| used. |
|
|
There is a refrigerant | Check for oil in chiller cabinet |
leak. | and bubbles in refrigerant site |
| glass. Consult Conair Service |
| for repair. |
|
|
The pressure switch is | See Checking Pressure |
Switches, in the | |
faulty. | Troubleshooting section. |
UGH016/0500 | Series 1 Portable Chillers, TIC Control TROUBLESHOOTING |