CONTROL
PROBLEMS
CONT’D
Symptom | Possible cause | Solution |
|
|
|
The control is lit and there is no alarm condition. The com- pressor hums, but does not run.
The input voltage is incorrect
There is a phase loss.
Check the main supply volt- age. It must be within 10% of the nameplate rating.
❐Check the fuses on the main power supply.
❐Check the
❐Check phase continuity
through the compressor con- tactor.
❐Check the wiring at the compressor.
Replace or repair as needed.
TROUBLESHOOTING Series 1 Portable Chillers, TIC Control | UGH016/0500 |