TROUBLESHOOTING & REPAIR
CONTROL TRANSFORMER (T2) TEST (continued)
5.Locate the control transformer secondary leads. See Figure F.10. Lead X1 is con- nected to the coil terminal on the CR1 input contactor. Lead X2 is spliced into lead #211, which is then connected to the input power switch (SW1).
WARNING
HIGH VOLTAGE is present at
the input leads.
6.Apply the correct
NOTE: The
7.If approximately 115 VAC is present at leads X1 to X2, the control transformer is function- ing properly.
8.If approximately 115 VAC is NOT present at leads X1 to X2, make certain the correct input voltage is being applied to the primary winding of the control transformer and that the correct primary leads (H1, H2, H3, etc.) are being used. See the connection infor- mation diagram on the input access door.
9.If the correct voltage is being applied to the primary of the control transformer and the secondary voltage is incorrect or not pre- sent, the control transformer may be defec- tive.