Emerson 1F92 manual Installer Table, Comments

Page 18

INSTALLER TABLE

NOTE: You must be in the User Configuration Menu to enter the Installer Menu. Press TIME FWD and TIME BACK at same time.

Step

Press Button(s)

Displayed (Factory Default)

Press

or

to select:

COMMENTS

See

Page

 

 

 

 

 

 

 

 

1

SET

TIME

HEAT PUMP

 

MLTI STG

 

Selects type of system. Selecting HEAT PUMP

14

 

and SET

DAY

 

 

 

 

makes additional menu items for heat pump

 

 

 

 

 

 

system available.

 

 

(hold for approx.

 

 

 

 

 

 

 

 

 

 

 

 

 

3 seconds)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

TIME

FWD

HEAT PUMP

 

2 or 3

 

Selects:

14

 

(Heat Pump ONLY)

(1)

 

 

 

1. one compressor on Y1.

 

 

 

 

 

 

 

 

2. two compressors on Y1, Y2.

 

 

 

 

 

 

 

 

3. one compressor on W1.

 

 

 

 

 

 

 

 

 

 

3

TIME

FWD

ELECT HEAT FAN

 

OFF

 

Fan cycles with call for heat if ON. Fan always

14

 

 

 

(ON)

 

 

 

cycles with pump stages.

 

 

 

 

 

 

 

 

4

TIME

FWD

SET CYCLE HEAT

1 to 40 for multi-stage

Selects HEAT anticipation adjustment.

14

 

 

 

(5 for multi-stage

9 to 40 for heat pump

 

 

 

 

 

13 for heat pump)

 

 

 

 

 

5

TIME

FWD

SET CYCLE COOL

 

9 to 40

 

Selects COOL anticipation adjustment.

14

 

 

 

(13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

TIME

FWD

SET CYCLE AUX

 

1 to 40

 

Selects AUXILIARY stage anticipation adjustment.

14

 

(Heat Pump ONLY)

(06)

 

 

 

(Heat Pump ONLY)

 

 

 

 

 

 

 

 

7

TIME

FWD

COOL FAN DELAY OFF

0 to 127 seconds

Selects time delay for COOL fan OFF.

18

 

 

 

(00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

Image 18
Contents Series Easy, Menu-Driven Set-Up Programming Introduction Orientation Thermostat ButtonsDisplay Electrical Data InstallationSpecifications Thermal DataPrecautions Installation Remove OLD ThermostatAttach Base to Wall Configuring Programming Thermostat base and terminalsMULTI-STAGE Terminal Outputs Thermostat Terminals UpperHeat Pump Terminal Outputs Malfunction Light Not Used Thermostat Terminals Lower Configuration Switches Reset Switch E2/P Switch Installer Configuration Entering the Configuration MenusElectric Heat FAN Configuration MULTI-STAGE/HEAT Pump ModeHeat Pump COMPRES- SOR Configuration SET Cycle HEAT, COOL, AUX AnticipationHeating Cooling Installer Table CommentsHeat Pump 1 Programmable Cool FAN-OFF and FAN-ON Delay Programmable Heat FAN-OFF DelayPump Fossil Fuel KIT Alternative Economizer Feature Compressor LockoutFAN Operation Heating SystemUntil FAN Auto Cooling System MULTI-STAGE/HEAT Pump Auxiliary Operation TestTroubleshooting Reset Button Resetting Thermostat Configuration and ProgrammingConfiguration User Menu Keypad Lockout Menu access from User Menu Entering Your Program To Set the Clock ProgrammingProgrammed Operation Planning Your Program To Set the DayFAN Day Sample Program Schedule Shows factory programming Day Personal Program Schedule Features Adjustable Temperature DisplaySelectable Energy Management Recovery EMR Heat Fast Fahrenheit or Celsius Tem- perature DisplaySingle Period Fan Control Cool FastActivate RUN PRG by Telephone Compressor Run Time Traditional Features Automatic ChangeoverFactory Preprogrammed Times and Temperatures Keypad LockoutCompressor Short-Cycle Protection Programmable Fan ControlAir Filter Change-Out Indicator System and Thermostat DiagnosticsTemporary Program Override Indefinite Program HoldProgrammable Vacation Time/ Temperature Operation Daylight Savings Time ButtonThermostat Startup After Total Power Loss Large Lighted Liquid Crystal Display LCDArm Chair Programming Second Stage Time Delay Features IndexPage Page Part no -6422C