Emerson 1F92 manual Cooling System, MULTI-STAGE/HEAT Pump Auxiliary Operation Test

Page 23

COOLING SYSTEM

!CAUTION

To prevent compressor and/or property damage, if the outdoor temperature is below 50°F (10°C), DO NOT operate the cooling system.

1.Press PROGRAM RUN .

2.Press SYSTEM until COOL is displayed.

3.Press to adjust thermostat setting below room temperature. The fan should come on (after the fan-on delay time, if any), followed by cold air circulation.

4.Press to adjust tempera- ture setting above room temperature. The cooling system should stop operating, and the fan should stop

running (after the fan-off delay time, if any).

MULTI-STAGE/HEAT PUMP AUXILIARY OPERATION TEST

Follow these steps to energize all stages of heat or cool to permit system checks during installation.

HEAT: Press to raise temperature setting to 99°F, then hold for five seconds. The second and third stage heat relays will energize immediately for test purposes. The LED indicator will glow green for first stage and yellow for second stage.

COOL: Press to lower temperature setting to 45°F, then hold for five seconds. The second stage cool relay will energize immediately for test purposes. The LED indicator will glow green for first stage and yellow for second stage.

EMERGENCY (heat pump only): Press SYSTEM to select EMER mode. The LED indicator will glow red for emergency mode. A flashing light indicates a malfunction in the system.

21

Image 23
Contents Series Easy, Menu-Driven Set-Up Programming Introduction Thermostat Buttons OrientationDisplay Thermal Data InstallationSpecifications Electrical DataPrecautions Attach Base to Wall InstallationRemove OLD Thermostat Thermostat base and terminals Configuring ProgrammingThermostat Terminals Upper MULTI-STAGE Terminal OutputsHeat Pump Terminal Outputs Malfunction Light Not Used Thermostat Terminals Lower E2/P Switch Configuration Switches Reset SwitchEntering the Configuration Menus Installer ConfigurationSET Cycle HEAT, COOL, AUX Anticipation MULTI-STAGE/HEAT Pump ModeHeat Pump COMPRES- SOR Configuration Electric Heat FAN ConfigurationHeating Cooling Comments Installer TableHeat Pump 1 Pump Fossil Fuel KIT Alternative Programmable Cool FAN-OFF and FAN-ON Delay Programmable Heat FAN-OFF Delay Compressor Lockout Economizer FeatureUntil FAN Auto FAN OperationHeating System MULTI-STAGE/HEAT Pump Auxiliary Operation Test Cooling SystemResetting Thermostat Configuration and Programming Troubleshooting Reset ButtonConfiguration User Menu Keypad Lockout Menu access from User Menu To Set the Day ProgrammingProgrammed Operation Planning Your Program Entering Your Program To Set the ClockFAN Day Sample Program Schedule Shows factory programming Day Personal Program Schedule Selectable Energy Management Recovery EMR FeaturesAdjustable Temperature Display Cool Fast Fahrenheit or Celsius Tem- perature DisplaySingle Period Fan Control Heat FastKeypad Lockout Traditional Features Automatic ChangeoverFactory Preprogrammed Times and Temperatures Activate RUN PRG by Telephone Compressor Run TimeProgrammable Fan Control Compressor Short-Cycle ProtectionSystem and Thermostat Diagnostics Air Filter Change-Out IndicatorIndefinite Program Hold Temporary Program OverrideDaylight Savings Time Button Programmable Vacation Time/ Temperature OperationArm Chair Programming Thermostat Startup After Total Power LossLarge Lighted Liquid Crystal Display LCD Second Stage Time Delay Index FeaturesPage Page Part no -6422C