Envision Peripherals IM1609 08, IM1609 10 Open Loop Ground Water Systems, Water Quality

Page 18

ENVISION CONSOLE INSTALLATION MANUAL

Open Loop Ground Water Systems

Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 GPM of flow per ton of cooling capacity is recommended in open loop applications.

Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.

Note: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW1-Switch #2 to the “WELL” position (Refer to the Dip Switch Field Selection table). Slow opening/closing solenoid valves (type VM) are recom- mended to eliminate water hammer.

Water Quality

In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing.

Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.

17

Image 18
Contents Envision Console Installation Manual Page Table of Contents Model Nomenclature NC CRefrigerant Systems General Installation InformationSafety Considerations Moving and StorageDimensional Data Flat Top Cabinet NCW09-18NCS09-18 Dimensional Data Slope Top CabinetConfiguration Slope TopDimensional Data Extended Slope Top Cabinet NCE09-18Ext. Slope Top Dimensional Data Right Return Controls Detail Dimensional Data Right Return Chassis Dimensional Data Left Return Controls Detail Dimensional Data Left Return Chassis #Installation Steps Mark Unit PositionProvide Water and Condensate Drain Connections Pipe LocationsFinal Electrical Connection Provide Line Voltage WiringChassis Installation Final Water ConnectionField Converting Console Top view Side viewSystem Cleaning and Flushing Cleaning and FlushingGround Source Loop System Checkout Open Loop Ground Water Systems Water QualityAuxiliary Heat Ratings Microprocessor Remote Thermostat WiringElectrical Connections GeneralUnit Electrical Data Fan Performance DataWiring Schematic 208-230-265/60/1CCM w/EH Electronic Thermostat 208-230-265/60/1 Control ModuleLED Display Mode Table 208-230-265/60/1 Schematic a Versatec Control EH & Remote Wall ThermostatFX10 EH 208-230-265/60/1 PSCStandard CCM Control Features Envision Console ControlsOptional Versatec Microprocessor Control Features Logic Board DIP Switch Settings Control Tables for Optional Versatec MicroprocessorOptional FX10 Control Optional FX10 Microprocessor and BAS Interface Control Timing & Fault Recognition DelaysStandard Features Zone SensorsControl and Safety Feature Details Sequence of OperationCompressor Minimum On Delay Random Start DelayCompressor Fixed On Delay Time Compressor Short Cycle Delay TimeInputs & Outputs Configuration Control AccessoriesInfo Status Temps Outputs Settings FX10 User Interface MUI Physical Layout Login Required N2 Open LonWorks LonWorks Point DescriptionBACNet BACnet Point DescriptionAnalog Output Type BACnet VariablesAnalog Input Type Analog Value TypeMultistate Input Type Multistate Output TypeEmergency Electric Resistance Heat Hydronic Loop Controller for Boiler/Tower InstallationsUnit Startup Notes Electrical DisconnectUnit Startup Checklist / Unit Startup Steps Before Powering Unit, Check The FollowingStartup Steps Unit Operating Parameters Unit Operating LimitsSingle Speed Models Startup/Troubleshooting Form Pressure Drop Water Coil Maintenance Preventive MaintenanceReplacement Procedures Other MaintenancePage Envision Series Console

IM1609 10, IM1609 08 specifications

Envision Peripherals has carved a niche in the realm of advanced display technology, and its IM1609 10 and IM1609 08 models are no exception. These cutting-edge monitors are designed to meet a wide array of professional needs while delivering outstanding performance and visual clarity.

One of the standout features of the IM1609 10 is its impressive 16:9 aspect ratio and full HD resolution. This setup ensures that users receive crisp and vibrant visuals, whether they're working on intricate designs, analyzing data, or enjoying multimedia content. The IM1609 08 shares similar visual capabilities, making both models ideal for professionals in graphic design, video editing, and other visually intensive fields.

Both displays incorporate advanced LED backlight technology, which not only enhances color accuracy but also contributes to energy efficiency. Users can expect deeper blacks and brighter whites, resulting in a more dynamic visual experience. Furthermore, the IM1609 series features wide viewing angles, allowing multiple users to view the screen simultaneously without loss of quality or color distortion.

In terms of connectivity, the IM1609 10 and IM1609 08 come equipped with a range of ports, including HDMI, DisplayPort, and USB-C. This versatility ensures seamless integration with various devices, from laptops and desktops to media players and more. The USB-C port also allows for quick data transfer and charging options, catering to the needs of modern tech users.

Ergonomics is another key characteristic of the IM1609 series. With adjustable stands that allow for height, tilt, and swivel adjustments, users can customize their viewing experience for maximum comfort, reducing neck and eye strain during long working hours.

Additionally, the IM1609 monitors feature built-in blue light filters and flicker-free technology, which help to create a healthier viewing environment by minimizing eye fatigue. This consideration for user well-being is increasingly important in today’s tech-driven world, especially for professionals who spend significant time in front of screens.

Overall, Envision Peripherals’ IM1609 10 and IM1609 08 models represent the company’s commitment to blending performance, usability, and comfort into one seamless package. Whether for professional or personal use, these monitors deliver exceptional quality, making them a noteworthy addition to any workspace.