Envision Peripherals IM1609 10, IM1609 08 installation manual LED Display Mode Table

Page 23

ENVISION CONSOLE INSTALLATION MANUAL

Wiring Schematic

VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT Legend for Schematic [A]

 

Normal Control Timing Table

Blower off delay

30 seconds

208-230-265/60/1

Versatec Logic Board Physical Layout

 

 

 

Compressor on delay

10 seconds

 

Short cycle delay

5 minutes

 

Minimum compressor on time

60 seconds (except for fault condition )

 

High pressure fault recognition delay

Less than 1 second

 

Low pressure fault recognition delay

30 seconds

 

Freeze sensing fault recognition delay

30 seconds

 

Condensate overflow fault recognition delay

30 seconds

 

Low pressure fault bypass delay

2 minutes

 

Freeze sensing fault bypass delay

2 minutes

 

Motorized valve delay

90 seconds

 

Random start delay

0 - 25 seconds

 

Test Control Timing Table

 

Blower off delay

5 seconds

 

Compressor on delay

2 seconds

 

Short cycle delay

15 seconds

 

Minimum compressor on time

5 seconds (except for fault condition )

 

High pressure fault recognition delay

Less than 1 second

 

Low pressure fault recognition delay

30 seconds

 

Freeze sensing fault recognition delay

30 seconds

 

Condensate overflow fault recognition delay

30 seconds

 

Low pressure fault bypass delay

0 seconds

 

CC CCG C

C

R

R

P3

Fan Relay

FAN FANCOM

Microprocessor

Logic Control

17P529A01

CC Relay

6

 

 

 

1

 

 

7

 

 

2

 

 

8

 

P2

 

 

3

 

9

 

 

4

 

 

10

 

 

5

 

 

 

 

 

SW1

Freeze sensing fault bypass delay

0 seconds

Motorized valve delay

90 seconds

Random start delay

0 seconds

 

LED Display Mode Table

 

LED

Normal Display Mode

 

 

 

SW1 - #4 On, SW2 Off

 

 

Drain

Drain pan overflow lockout

 

 

 

 

 

 

Water Flow

FS thermistor (loop <15°F, well < 30°F) lockout

 

 

 

 

 

 

High Press

High pressure >600 PSI lockout

 

 

 

 

 

 

Low Press

Low pressure < 40 PSI lockout

 

 

 

 

 

 

Air Flow

Not used

 

 

 

 

 

 

Status

Microprocessor malfunction*

 

 

 

 

 

 

DHW Limit

Not Used

 

 

 

 

 

HWD

SW2 status (Off = down position, On = up position)

 

 

 

 

 

 

 

 

 

 

 

Diagnostic Modes

 

LED

Current Fault Status

 

Inputs

Outputs

 

SW1- #4 On, SW2 On

 

SW1- #4 Off, SW2 Off

SW1- # 4 Off, SW2 On

Drain

Drain pan overflow

 

Y

Compressor

Water Flow

FS thermistor (loop <15°F, well <30°F)

 

G

FAN

High Press

High pressure > 600 PSI

 

O

O

Low Press

Low pressure < 40 PSI

 

ES

ES

Air Flow

Not used

 

NS

NS

Status

Not used

 

LS

LS

DHW Limit

Not used

 

Not Used

Not Used

HWD

SW2 in the On position

 

Off position

On position

*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a microprocessor malfunction.

P1

R

C

Y O

G LO ES NS LS

Logic Board DIP Switch Settings

 

Switch

 

 

OFF

 

 

ON

 

 

 

 

 

 

 

 

 

 

SW1 - 1

Test - Selected timings sped up to facilitate

 

Normal - Standard timings

 

 

troubleshooting

 

 

 

 

 

 

 

 

 

SW1 - 2

Loop - Closed loop freeze sensing setting (15°F)

Well - Open loop freeze sensing setting (30°F)

 

 

 

 

 

 

SW1 - 3

Enables NS features

 

Normal - Standard thermostat operation

 

 

 

 

 

 

 

 

SW1 - 4

IO Display * - Enables Input/Output display on external

Normal * - Unit status display

 

 

LED board*

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1 - 5

Motorized Valve - 1.5 minute compressor on delay

Normal - Standard delay on call from

 

compressor used

 

 

 

 

 

 

 

 

 

 

SW2

OFF * - Normal or Input display mode activated

ON * - Current fault or Output display

 

mode activated

 

 

 

 

 

 

 

*Refer to LED Display Mode table for position of SW1-4 and SW2

 

 

 

 

 

Operational Logic Table

 

 

Mode

 

Inputs

 

Fan

 

Comp

 

RV

 

Htg

 

Y

 

ON

 

ON

 

OFF

 

Clg

 

Y,O

 

ON

 

ON

 

ON

 

Fan

 

G

 

ON

 

OFF

 

OFF

22

Image 23
Contents Envision Console Installation Manual Page Table of Contents NC C Model NomenclatureMoving and Storage General Installation InformationSafety Considerations Refrigerant SystemsNCW09-18 Dimensional Data Flat Top CabinetSlope Top Dimensional Data Slope Top CabinetConfiguration NCS09-18Ext. Slope Top Dimensional Data Extended Slope Top CabinetNCE09-18 Dimensional Data Right Return Controls Detail  Dimensional Data Right Return ChassisDimensional Data Left Return Controls Detail # Dimensional Data Left Return ChassisMark Unit Position Installation StepsPipe Locations Provide Water and Condensate Drain ConnectionsFinal Water Connection Provide Line Voltage WiringChassis Installation Final Electrical ConnectionTop view Side view Field Converting ConsoleGround Source Loop System Checkout System Cleaning and FlushingCleaning and Flushing Water Quality Open Loop Ground Water SystemsGeneral Microprocessor Remote Thermostat WiringElectrical Connections Auxiliary Heat RatingsFan Performance Data Unit Electrical Data208-230-265/60/1 Wiring SchematicControl Module CCM w/EH Electronic Thermostat 208-230-265/60/1LED Display Mode Table Versatec Control EH & Remote Wall Thermostat 208-230-265/60/1 Schematic aPSC FX10 EH 208-230-265/60/1Envision Console Controls Standard CCM Control FeaturesOptional Versatec Microprocessor Control Features Control Tables for Optional Versatec Microprocessor Logic Board DIP Switch SettingsOptional FX10 Control Zone Sensors Control Timing & Fault Recognition DelaysStandard Features Optional FX10 Microprocessor and BAS InterfaceSequence of Operation Control and Safety Feature DetailsCompressor Short Cycle Delay Time Random Start DelayCompressor Fixed On Delay Time Compressor Minimum On DelayControl Accessories Inputs & Outputs ConfigurationFX10 User Interface MUI Physical Layout  Info Status Temps Outputs SettingsLogin Required N2 Open LonWorks Point Description LonWorksBACnet Point Description BACNetAnalog Value Type BACnet VariablesAnalog Input Type Analog Output TypeMultistate Output Type Multistate Input TypeElectrical Disconnect Hydronic Loop Controller for Boiler/Tower InstallationsUnit Startup Notes Emergency Electric Resistance HeatStartup Steps Unit Startup Checklist / Unit Startup StepsBefore Powering Unit, Check The Following Single Speed Models Unit Operating ParametersUnit Operating Limits Startup/Troubleshooting Form Pressure Drop Other Maintenance Preventive MaintenanceReplacement Procedures Water Coil MaintenancePage Envision Series Console

IM1609 10, IM1609 08 specifications

Envision Peripherals has carved a niche in the realm of advanced display technology, and its IM1609 10 and IM1609 08 models are no exception. These cutting-edge monitors are designed to meet a wide array of professional needs while delivering outstanding performance and visual clarity.

One of the standout features of the IM1609 10 is its impressive 16:9 aspect ratio and full HD resolution. This setup ensures that users receive crisp and vibrant visuals, whether they're working on intricate designs, analyzing data, or enjoying multimedia content. The IM1609 08 shares similar visual capabilities, making both models ideal for professionals in graphic design, video editing, and other visually intensive fields.

Both displays incorporate advanced LED backlight technology, which not only enhances color accuracy but also contributes to energy efficiency. Users can expect deeper blacks and brighter whites, resulting in a more dynamic visual experience. Furthermore, the IM1609 series features wide viewing angles, allowing multiple users to view the screen simultaneously without loss of quality or color distortion.

In terms of connectivity, the IM1609 10 and IM1609 08 come equipped with a range of ports, including HDMI, DisplayPort, and USB-C. This versatility ensures seamless integration with various devices, from laptops and desktops to media players and more. The USB-C port also allows for quick data transfer and charging options, catering to the needs of modern tech users.

Ergonomics is another key characteristic of the IM1609 series. With adjustable stands that allow for height, tilt, and swivel adjustments, users can customize their viewing experience for maximum comfort, reducing neck and eye strain during long working hours.

Additionally, the IM1609 monitors feature built-in blue light filters and flicker-free technology, which help to create a healthier viewing environment by minimizing eye fatigue. This consideration for user well-being is increasingly important in today’s tech-driven world, especially for professionals who spend significant time in front of screens.

Overall, Envision Peripherals’ IM1609 10 and IM1609 08 models represent the company’s commitment to blending performance, usability, and comfort into one seamless package. Whether for professional or personal use, these monitors deliver exceptional quality, making them a noteworthy addition to any workspace.